期刊文献+

夏季新型混合地源热泵系统经济性分析 被引量:4

Economic Analysis on the New Hybrid Ground Source Heat Pumps System in Summer
下载PDF
导出
摘要 我国南方地区商业、办公建筑由于冷热负荷差值较大,导致其传统地源热泵系统运行效率较低.本文对长沙地区湘江边的一栋办公大楼,选用新型混合地源热泵系统与传统地源热泵系统进行夏季能耗编程模拟并进行对比.结果显示采用新型混合地源热泵系统比采用传统的地源热泵系统的初投资节省约14%,运行费用节省3.9%~6.5%,且该系统的运行效率在采用流入机组水温作为控制参数时达到最高. In commercial and office buildings located in the South of China,the efficiency of traditional ground source heat pumps system is low because of the big difference of cooling and heating loads.The energy simulation by computer programming method was done for an office building beside the Xiang River in Changsha,where the energy consumption of the conventional ground-source heat pump system was compared with that of the new hybrid ground-source heat pump system in summer.The result shows that it can save 14% of initial investment,3.9%~6.5% of running cost if the new hybrid ground-source heat pump system is used,and the efficiency of new hybrid ground-source heat pump system gets to the highest when the temperature of water into the units is taken as the control parameter.
出处 《湖南大学学报(自然科学版)》 EI CAS CSCD 北大核心 2009年第S2期114-118,共5页 Journal of Hunan University:Natural Sciences
基金 教育部高等学校博士学科点专项基金资助项目(20060532015)
关键词 混合热泵系统 水源辅助散热 能耗模拟 控制策略 hybrid ground source heat pumps supplemental heat rejecter using water energy simulation control
  • 相关文献

参考文献8

二级参考文献42

  • 1杨大明.21世纪的绿色空洞技术——地源热泵[J].内蒙古科技与经济,2002(9):10-11. 被引量:8
  • 2于立强.水-水活塞压缩式热泵机组的性能测试[J].暖通空调,1995,25(1):12-14. 被引量:9
  • 3朱金鸣,项弸中.江水源热泵在上海十六铺工程中的应用[J].暖通空调,2007,37(2):88-93. 被引量:13
  • 4Parson R. ASHRAE Handbook-Fundamentals. Atlanta ( USA ) : ASHRAEInc, 1985, Chapter2.
  • 5成都簇锦房地产开发有限公司.成都龙锦慧苑地源热泵运行技术经济分析.建筑节能,2006,:26-27.
  • 6盛晓文.供热技术经济学[M].哈尔滨:哈尔滨工业大学出版社.2005.
  • 7马最良 姚杨.民用建筑空调设计[M].北京:化学工业出版社,2002..
  • 8ASHRAE, Commercial/institutional ground source heat pumps engineering manual [M]. Atlanta: American Society of Heating,Refrigeration and Air-Conditioning Engineers, 1995.
  • 9S P Kavanaugh. A design method for hybrid ground-source heat pumps [J]. ASHRAE Transactions, 1999, 104(2): 691-698.
  • 10G Phetteplace, W Sullivan. Performance of a hybrid ground-coupled heat pump system [J]. ASHRAE Transactions,1998,104(1b): 763-770.