直流输电系统接地极电流对交流电网的影响分析 被引量:163

ANALYSIS ON INFLUENCE OF GROUND ELECTRODE CURRENT IN HVDC ON AC POWER NETWORK
下载PDF
导出
摘要 基于三广直流输电系统(三峡广东高压直流输电工程)的调试结果,分析了有多个直流系统落点的交流电网中直流接地极电流对交流电网影响的基本规律。提出为减小直流接地极电流对交流电网的影响应合理安排直流系统的运行方式;建立可靠的电流通道,减小接地极的接地电阻或建立专门线路;合理安排电网中交流变压器的接地点和接地方式。文章介绍了实施上述措施需进行的具体研究工作。 Based on the commissioning test results of the HVDC from Three Gorges hydro power station to Guangdong power network, the basic law of the influence of DC ground electrode current on AC power network, in which multi-HVDC receiving ends exist, is analyzed. To reduce this influence, it is necessary to rationally arrange the operating mode of the HVDC, build reliable current channel, reduce the grounding resistance of ground electrode, rationally configure the grounding points and grounding modes of AC transformers in AC power network, etc. The concrete study items of these measures to be performed are presented.
作者 王明新 张强
出处 《电网技术》 EI CSCD 北大核心 2005年第3期9-14,共6页 Power System Technology
关键词 直流输电系统 接地极电流 交流电网 电力系统 Electric currents Electric power generation Electric power transmission Electric resistance Electric transformers Grounding electrodes
  • 相关文献

参考文献9

二级参考文献29

  • 1许崇武 胡学文 彭泉光 等.接地网防蚀研究及应用[R].武汉:武汉水利电力大学,2000..
  • 2.DL755-2001.电力系统稳定导则[s].,..
  • 3[1]Asplund G,Eriksson K et al.Dc Transmission based on voltage source converters[C].CIGRE,1998.
  • 4[2]Stendius L,Eriksson K.HVDC Light --An excellent tool for city center infeed[C].PowerGen Conference,Singapore,1999.9.
  • 5[3]Grünbaum R,Halvarsson B,Wilk-Wilczynski A.FACTS and HVDC light for power system interconnections[C].Power Delivery Conference,Madrid,Spain,1999.9.
  • 6[4]Lei X,Lerch E,Povh D et al.A large integrated power system software package - NETOMAC[C].Proceedings of POWERCON'98, Beijing,China:17~22.
  • 7[5]Zhang Guibin,Xu Zheng.Steady-state model for VSC based HVDC and its controller design[C].IEEE PES Winter meeting 2001,Columbus Ohio,USA,Jan.28-Feb.1.
  • 8[3]Kezunovic M, Guo Y. Modeling and simulation of the power transformer faults and related protective relay behavior[J]. IEEE Trans on Power Delivery, 2001, 15(1): 44-49.
  • 9[7]BastardP, BertrandP, MeunierM. A transformer model for winding fault studies[J], IEEE Trans on Power Delivery, 1994, 9(2): 690-699.
  • 10[3]Johnson R K, Klemn N S, Schilling K H. Power modulation of Sidney HVDC themes, Part I & Part Ⅱ[J]. IEEETrans on Power Delivery,1989, 4(4): 2145-2161.

共引文献326

同被引文献1130

引证文献163

二级引证文献1794

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部