摘要 基于电场有限元数值计算和界面沿面放电试验研究结果,研制了优化绝缘结构设计的插拔式快速终端和接头,其应力锥的绝缘材料采用三元乙丙橡胶,外屏蔽为不锈钢。,终端和中间接头插拔配合的过盈值、复合界面压强值的理论计算值和按IEC、GB、Q/WLT等标准进行型式和补充试验的结果基本一致,寿命可达1000次。 Design of termination and joint for pass-by cable used to living-work had been optimized based on FEM analysis and study results of surface discharge experiments in this paper. According to IEC 60502 standard, type test and complementary tests including inserted in and drawn out 1000 times fatigue test for validating their electrical characteristics are discussed in the paper. The research results prove that power cable with rated voltage up to 35 kV may be connected and/or branched on-site quickly and safely using these terminations and joints.
出处 《高电压技术》 EI CAS CSCD 北大核心 2005年第5期50-51,54,共3页 High Voltage Engineering
关键词 电力电缆 终端和接头 带电作业 power cable, termination & joint living work
  • 相关文献

参考文献9

二级参考文献4

  • 1N Morales, et al. Field solution in polluted insulators with non-symmetric boundary conditions [J]. IEEE Trans. On Dielectric and Electrical Insulation, 2001,8(2): 168-172.
  • 2武汉高压所,全国电缆运行工作网1996—2001年全国电力系统电力电缆运行故障统计资料,2000年
  • 3陈季丹,电介质物理学,1982年
  • 4史济康,曹家,袁检,罗俊华,胡文康.XLPE电力电缆中间接头复合介质沿面放电研究[J].高电压技术,2001,27(4):52-53. 被引量:50