期刊文献+

低气压下三种覆冰支柱绝缘子直流闪络特性研究 被引量:24

STUDY ON DC FLASHOVER PERFORMANCE OF THREE TYPES OF ICED POST INSULATORS AT LOWER ATMOSPHERIC PRESUURE
下载PDF
导出
摘要 根据人工气候试验室内三种支柱绝缘子的人工覆冰直流闪络试验结果,分析了低气压下覆冰对支柱绝缘子直流闪络特性的影响。结果表明:不同伞裙结构对重冰条件下的三种支柱绝缘子的直流闪络电压影响不明显,但对临界闪络电流的影响较大;低气压下,三种支柱绝缘子的闪络电压和临界闪络电流下降明显;三种绝缘子覆冰闪络的极性效应不明显。 Based on the DC flashover test results of three types of iced post insulators at lower atmospheric pressure in the artificial climate chamber, this paper analyzes the effect of ice on the DC flashover performance of iced post insulators. The influence of the contours and sizes of sheds on the flashover voltages and the critical flashover currents at severely icing condition is obtained. There is an obvious degradation of the flashover voltages and the critical flashover currents at lower air pressure. And it is found that the polarity effect is not obvious.
出处 《中国电机工程学报》 EI CSCD 北大核心 2005年第15期12-15,共4页 Proceedings of the CSEE
基金 国家自然科学基金重大研究计划项目(90210026)。~~
关键词 支柱绝缘子 输电线路 覆冰 直流 闪络 Post insulator Transmission line Icing DC Flashover
  • 相关文献

参考文献17

二级参考文献23

  • 1舒立春,孙才新,顾乐观.覆冰、低气压下染污绝缘子的交流闪络特性[J].高电压技术,1995,21(2):14-18. 被引量:17
  • 2蒋兴泉 易辉.输电线路覆冰及防护[M].中国电力出版社,2002..
  • 3[6]Li Yu.Study of the influence of altitude on the characteristies of the electrical arc on polluted ice surface[D].Canada:Universite de Quebec a Chicoutimi,2002.
  • 4[7]Sun Caixin,Jiang Xingliang,Sima Wenxia,et al.Study of flashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[J].IWAIS 2002,Bmo,Czech Republic,2002.
  • 5[9]Phan L C,Matsuo H.Minimum flashover voltage of iced insulators [J].IEEE Transactions on Electrical Insulation,1983,(EI-18)6:605-618.
  • 6栗福珩,高电压技术,1991年,1页
  • 7Chen Xing . Modeling of electrical arc on polluted ice surface[D]. Canada: University of Quebec in Chicoutimi, 2000.
  • 8Farzaneh M, Zhang J. Behavior of DC arc discharge on ice surface[C]. Proceedings of 8th international workshop on the atmospheric icing of structure, Iceland, 1998.
  • 9Cai-xin S, Xing-liang J, Wen-xia S, et al. Study of fiashover performance and voltage correction of DC insulator in icing districts of altitude of 2500m and below[C]. Proceedings of 10th IWAIS, Brno,Czech Repubic, 2002.
  • 10Jiang Xingliang, Sun Caixin, Sima Wenxia, et al. AC flashover performance and voltage correction of 27.5 and 110 kV iced composite insulator at atmospheric pressure of 4000~5500m high altitude districts[C]. IEEE Powercon'2002, Brno, Czech Repubic,2002.

共引文献256

同被引文献321

引证文献24

二级引证文献352

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部