期刊文献+

一种基于波形相关分析识别变压器励磁涌流的方法 被引量:10

A measure to identify the inrush current of transformer based on wave correlation analysis
下载PDF
导出
摘要 提出了一种基于波形相关分析识别变压器励磁涌流的方法。该方法首先用线性插值法找出保护启动后最近的差流过零点,然后利用数字信号处理中相关函数的基本原理对采样数据进行分析,计算过零点后一周波中前后半波的自相关系数,根据自相关系数的大小构成区分励磁涌流和故障电流的主判据。动模试验结果表明该方法算法简单,原理清楚,识别正确,具有较高的可靠性和灵敏性。 A new scheme based on wave correlation analysis to distinguish the inrush and internal fault occurred in the transformer is proposed.Firstly, it is to find out the zero-crossing of the differential current using the linear interpolation method after the protection has enabled. Then it is to calculate self-correlation coefficients of the former semiwave and the backward semiwave after analyzing the sampling data. According to the magnitudes of the calculated coefficients, inrush current and fault current of transformer can be distinguished. The results of dynamic simulation verify the feasibility of the proposed method. Meanwhile, dynamic model test indicates that this algorithm has a simple calculation and its principle is clear.
作者 安源 刘家军
出处 《继电器》 CSCD 北大核心 2007年第18期1-5,共5页 Relay
关键词 变压器 过零点 相关系数 励磁涌流 transformer zero-crossing correlation coefficient inrush current
  • 引文网络
  • 相关文献

参考文献5

  • 1Sharp R L,Glassburn W E.A Transformer Differential Relay with Second Harmonic Restraint[J].IEEE Trans on PAS,1958,(12):913-918.
  • 2LIU Pei,Malik O P,CHEN De-shu.Improved Operation of Differential Protection of Power Transformers for Internal Fault[J].IEEE Trans on Power Delivery,1992,7(4):1246-1251.
  • 3Phadke A G,Thorp J S.A New Computer-based Fluxrestrained Current-differential Relay for Power Transformer Protection[J].IEEE Trans on Power Appl Systems,1983,102(11):3624-3629.
  • 4Keizo,Masaru H,Yoshiaki M,et al.Digital Protection Method for Power Transformers Based on an Equivalent Circuit Composed of Inverse Inductance[J].IEEE Trans on Power Delivery,1988,3 (4):1501-1510.
  • 5李贵存,刘万顺,滕林,郑涛.基于波形相关性分析的变压器励磁涌流识别新算法[J].电力系统自动化,2001,25(17):25-28. 被引量:54

二级参考文献2

共引文献53

同被引文献54

引证文献10

二级引证文献62

;
使用帮助 返回顶部