2006年武汉市公共场所集中空调通风系统卫生状况分析 被引量:8

Hygienic Status of Ventilation Systems of Centralized Air Conditioners in Public places of Wuhan 2006
下载PDF
导出
摘要 目的了解武汉市公共场所集中空调通风系统污染状况,为制定防治策略提供科学依据。方法对武汉市38家公共场所的集中空调通风系统进行采样,共检测164个出风口,38个冷却塔。检测的污染物指标为可吸入颗粒物(PM10)、送风口细菌总数、风管内表面积尘量、风管内表面细菌总数、嗜肺军团菌。结果164个出风口样品中,PM10、送风口细菌总数、风管内表面积尘量、风管内表面细菌总数4个指标均合格的占70.12%;38件冷却塔水样品中,嗜肺军团菌检出率为63.16%。结论武汉市公共场所集中空调通风系统仍存在一定的污染,应加强卫生监督和监测。 Objective In order to explore the contamination situation of ventilation systems of centralized air conditioners in public places of Wuhan and provide scientific basis for constituting preventive strategy. Methods 38 public places were taken out and sampled in Wuhan, which the detection indexes were inhalable particle matter (PM10), total Count of germs of supply - air outlet, amount of dust particles from the inside surface of flue pipes, total count of germs from the inside surface of flue pipes, legionella pneumophila. 164 air outlets and 38 cooling towers were tested. Results Among 164 air outlets, qualified samples occupied 70. 12%. Legionella pneumophila was found in 63.16% water samples from 38 cooling towers. Conclusion There has been still some pollution in ventilation systems of centralized air conditioners in public places of Wuhan. Hygiene supervision and monitoring should be strengthened in Wuhan.
出处 《中国卫生工程学》 CAS 2008年第1期6-8,共3页 Chinese Journal of Public Health Engineering
关键词 集中空调通风系统 可吸入颗粒物 细菌总数 嗜肺军团菌 Ventilation systems of centralized air conditioner Inhalable particle matter Total count of germs Legionella pneumophila
  • 相关文献

参考文献3

二级参考文献8

  • 1李德福.空调通风系统清洗规范的制定和理解[J].清洗世界,2004,20(5):32-39. 被引量:5
  • 2徐文华,韩华.空调系统对室内空气质量的影响及改进对策[C].上海室内环境空气污染防治和对策研讨会文集,1998,19.
  • 3.公共场所集中空调通风系统卫生规范[S].[S].,2003..
  • 4Greig JE,Carnie JA,Tallis GF,et al.An outbreak of Legionnaires'disease at the Melbourne aquarium,April 2000:investigation and case-control studies[J].Med J Aust,2004,180(11):566-572.
  • 5Brown CM,Nuorti PJ,Breiman RF,et al.A community outbreak of Legionnaires' disease linked to hospital cooling towers:an epidemiological method to calculate dose of exposure[J].Int J Epidemiol,1999,28(2):353-395.
  • 6Castellani Pastoris M,Ciceroni L,Lo Monaco R,et al.Molecular epidemiology of an outbreak of Legionnaires' disease associated with a cooling tower in Genova-Sestri Ponente,Italy[J].Eur J Clin Microbiol Infect Dis,1997,16(12):883-892.
  • 7Pinar A,Ramirez JA,Schindler LL,et al.The use of heteroduplex analysis of polymerase chain reaction products to support the possible transmission of Legionella pneumophila from malfunctioning automobile air conditioner[J].Infect Control Hosp Epidemiol,2002,23(3):145-147.
  • 8刘信荣,李燕华.唐山市某学院一起集体嗜肺军团菌病爆发的流行病学调查[J].中华流行病学杂志,1990,11(5):278-280. 被引量:8

共引文献27

同被引文献147

引证文献8

二级引证文献55

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部