期刊文献+

±800kV特高压直流输电线路极间距离优化研究 被引量:13

Research on Optimization of Space between Polar Conductors for ±800 kV UHVDC Transmission Line
下载PDF
导出
摘要 对±800 kV特高压直流输电线路的极间距离优化进行了研究,通过分析最大合成电场强度、最大离子流密度、无线电干扰、可听噪声等电磁环境参数随线路极间距离的变化规律,得出目前的±800 kV特高压直流输电线路22 m极间距离具备优化空间,然后基于电磁环境、空气间隙、V串夹角、塔头布置等多方面因素的优化,将极间距离由传统22 m优化至19 m,并论述了极间距离优化的巨大经济效益。 This paper studies optimization of the space between polar conductors. Based on the calculation and analysis of the electromagnetic environment factors, such as the maximum electric field strength, the maximum ion current density, radio interference and audible noise in different spaces between polar conductors, it is found that the current 22 m space of the ±800 kV UHVDC Transmission Line can be reduced. Then, based on optimization of multiple factors such as electro-magnetic environment, air gap and arrangement of V type insulators and conductors on steel towers, the space between polar conductors is reduced from 22 m to 19 m. Substantial economical benefits of the space optimization is also described.
出处 《电网与清洁能源》 2012年第1期49-53,共5页 Power System and Clean Energy
关键词 特高压直流 极间距离 电磁环境 输电线路 UHVDC space between polar conductors electromagnetic environment transmission line
  • 相关文献

参考文献10

  • 1Kim Hyunook, Hao Oliver J. pH and Oxidation-reduction potential control strategy for optimization of nitrogen removal in an alternating aerobic-anoxic system [ J]. Water Environment Research, 2001, 73 ( 1 ): 95- 102
  • 2Lefevre F, Audic J M, Bujon B. Automatic regulation of activated sludge aeration-single-tank nitrification-denitrification [J]. Water Science & Technology, 1993, 28(10): 289-298
  • 3Rordrigues Ana C, Brito Antonio G, Melo Luis F. Posttreatment of a brewery wastewater using a sequencing batch reactor [ J]. Water Environment Research, 2001, 73 ( 1 ): 45-51
  • 4Pierson John A, Pavlostathis Spyros G. Real-time monitoring and control of sequencing batch reactors for secondary treatment of a poultry processing wastewater [ J]. Water Environment Researeh, 2000, 72(5): 585-592
  • 5中国电力工程顾问集团公司.±800kV溪洛渡送出工程可研报告[R].北京:中国电力工程顾问集团公司,2008.
  • 6黎小林,张波,王琦,何金良.特高压直流线路的场分布影响因素分析[J].高压电器,2006,42(6):407-409. 被引量:12
  • 7张芳杰,郝阳.±800kv云广线导地线选型报告[R].西安:西北电力设计院,2007.
  • 8朱永平.张芳杰.±800kV向上线导线截面及分裂方式的研究报告[R].西安:西北电力设计院,2008.
  • 9鞠勇,陆家榆,杨勇,等.溪洛渡一浙西±800kV直流线路极间距离、对地高度和走廊宽度优化研究[R].北京:中国电力科学研究院.2011.
  • 10张殿生.电力工程高压送电线路设计手册[M].2版.北京:中国电力出版社.2002.

二级参考文献8

  • 1吴桂芳.我国±500kV直流输电工程的电磁环境问题[J].电网技术,2005,29(11):5-8. 被引量:60
  • 2侯远航,邬雄,万保权,张广州,孙竹森,吴巾克.±500 kV直流线路极导线垂直排列的合成场强[J].高电压技术,2005,31(5):37-38. 被引量:16
  • 3DL436—1991.高压直流架空送电线路技术导则[S].
  • 4EPRI Report TR-102764. HVDC Transmission Line Reference Book[R]. EPRI, 1993.
  • 5Sarma P, Janischewskyj W. Analysis of Corona Losses on DC Transmission Lines, Part Ⅱ-Bipolar Lines [J]. IEEE Trans.PAS, 1969, 88(10): 1476-1 491.
  • 6EPRI Report EL-2257. Conductor Development [R], EPRI,1982.
  • 7Janischewskyj W, Gela G, Finite Element Solution for Electric Fields of Coronating DC Transmission Lines[J]. IEEE Trans. PAS, 1979, 98(3): 1 000-1 012.
  • 8傅宾兰.高压直流输电线路地面合成场强和离子流密度的计算[J].中国电机工程学报,1987,29(5):5-8.

共引文献15

同被引文献144

引证文献13

二级引证文献49

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...