比较了双馈风电机组详细模型和通用模型的结构,发现通用模型中忽略了变流器、网侧控制器以及发电机的定转子动态。基于特征根技术及时域仿真分析,得出结论:通用模型中忽略变流器及网侧控制器的动态是合理的;通用模型中忽略发电机的定子及转子动态,仅对转子侧控制器的电气快动态有一定的影响。文中进一步指出,通用模型中还可忽略转子侧控制器电流控制内环的动态。文中还讨论了不同驱动系统模型下双馈风电机组动态特性的差异,以及转子侧控制器参数对双馈风电机组动态特性的影响。
The detailed model structure and generic model structure of doubly-fed induction generator (DFIG)-based wind turbines are compared. It is found that the capacitor, grid-side converter controller, and stator and rotor dynamics of the generator are ignored in generic model. Based on the eigenvalue technology and time-domain simulation analysis, it is reasonable to neglect the dynamics of capacitor and grid-side converter controller. The analysis also shows that negligence of stator and rotor dynamics of the generator in the generic model only has impact on the fast dynamics of rotor side controller. This paper further indicates that the generic model can also ignore the dynamics of current control inner-loop of rotor-side controller. The dynamic behaviors of different drive system models, and the impact of rotor-side controller parameters on the dynamic behavior of DFIG-based wind turbines is also studied. This work is supported by National Basic Research Program of China (973 Program)(No. 2013CB228204), National High Technology Research and Development Program of China (863 Program) (No. 2011AA05A103) and National Natural Science Foundation of China (No. 51190102, No. 51137002, No. 51207045).
出处
《电力系统自动化》
EI
CSCD
北大核心
2015年第5期7-14,共8页
Automation of Electric Power Systems
基金
国家重点基础研究发展计划(973计划)资助项目(2013CB228204)
国家高技术研究发展计划(863计划)资助项目(2011AA05A103)
国家自然科学基金资助项目(51190102
51137002
51207045)~~
关键词
双馈风电机组
详细模型
通用模型
动态特性
doubly-fed induction generator (DFIG) based wind turbines
detailed model
generic model
dynamic behavior