期刊文献+

500kV断路器失灵保护误动作跳闸故障分析 被引量:1

Trip Fault Analysis on Maloperation of 500 kV Breaker Failure Protection
下载PDF
导出
摘要 针对500 kV断路器失灵保护误动作问题,从故障时刻断路器状态及继电器触点直阻等方面进行分析,认为启动失灵继电器背板触点接触不良是导致故障的原因,提出使用更为可靠的备用触点的处理措施,并通过回路传动试验,验证了断路器启动失灵继电器正确动作,确保失灵保护装置平稳运行。 In view of the malfunction of the 500 kV circuit breaker failure protection, the analysis is carried out from the aspects of the circuit breaker state at the time of the failure and the direct resistance of the relay contact. It is considered that the poor contact of the backplane contact of the start failure relay is the cause of the failure, and the use of a more reliable backup contact is proposed. The corrective actions of the circuit breaker start failure relay have been verified through the circuit transmission test and the smooth operation of the failure protection device.
作者 陈天英 李铁成 王献志 侯仰军 CHEN Tianying;LI Tiecheng;WANG Xianzhi;HOU Yangjun(State Grid Hebei Electric Power Research Institute,Shijiazhuang 050021,China;Hebei Huadian Shijiazhuang Thermal Power Co.,Ltd.,Shijiazhuang 050041,China)
出处 《河北电力技术》 2021年第2期49-51,共3页 Hebei Electric Power
关键词 断路器 失灵保护 误动作 跳闸 circuit breaker failure protection malfunction trip
  • 相关文献

参考文献3

二级参考文献30

共引文献22

同被引文献14

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部