摘要
通过某发电厂220 kV线路接地故障时的录波数据,对发电厂内各机组的故障特征进行分析,利用录波数据校核了继电保护整定计算书中的接地短路电流,计算并分析各机组故障电流的特征,发现了两台发电机定子接地保护中性点零序电压变比不一致的问题,分析了系统接地故障对厂用400 V设备的影响等。
Based on the recorded wave data of a 220 kV line grounding fault in a power plant,the fault characteristics of equipment in each of its units are analyzed.The grounding short circuit current in the relay protection setting calculation sheet is checked by using the recorded wave data.The characteristics of fault current for each unit are calculated and analyzed.The problem is found out that the neutral point zero-sequence voltage transformation ratio of the stator grounding protection of two generators is inconsistent,and analyses are conducted on the influence of a system grounding fault on 400 V plant equipment,etc.
作者
吴小梦
WU Xiaomeng(Power Maintenance Company of Huaneng Hainan Power Generation Co.,Ltd.,Haikou 570311)
出处
《电力安全技术》
2022年第10期21-26,共6页
Electric Safety Technology
关键词
接地故障
故障特征
称分量分析法
等值阻抗
低电压穿越
grounding fault
fault characteristics
weighted component analysis
equivalent impedance
lowvoltage ride-through