摘要
零序功率方向继电器是线路保护中的一个重要元件。文中用六序分量法分析了同杆双回线上零序功率方向继电器的性能。结果表明 ,在同杆双回线上发生三相三导线及三相四导线故障、三相五导线跨线故障时 ,有一回线的零序功率方向会拒动。动模试验证实了理论分析的结果。
The zero sequence directional relay is an important relay component for transmission line. Based on the method of six sequence fault component, this paper analyses the performance of zero sequence directional relay on double circuit line on the same pole (DLSP). The result shows that faults, including three phases for three conductors or three phases for four conductors or three phases for five conductors faults, will be wrongly judged as the reverse faults by the zero sequence directional relay on one single circuit line of the DLSP. The dynamic simulation results prove the conclusion.
出处
《电力系统自动化》
EI
CSCD
北大核心
2002年第22期45-48,共4页
Automation of Electric Power Systems
关键词
零序功率方向继电器
误判
继电保护
同杆双回线
输电线路
线路保护
电力系统
protective relaying
zero sequence directional relay
double circuit line on the same pole (DLSP)
six sequence fault component