期刊文献+

变风量末端装置风量传感特性的试验研究 被引量:5

Experimental Study on the Air Flow Sensing Characteristics of VAV Terminal Device
下载PDF
导出
摘要 对变风量末端装置在不同工况下的风量传感特性进行了试验研究。结果表明,小风量、高静压、风管局部构件和较短的进口直管段长度等因素都会对风量传感器的传感特性产生不利影响;整流装置能很好地保证风量测量的准确性,这对缩短末端装置前的直管段长度,减少工程安装所占用的空间是十分有利的。 By analyzing the result of an experimental study on the air flow sensing characteristics of VAV terminal device under different conditions,the result showed that small air flow rate,high static pressure,local duct component and short length of straight inlet duct and other factors make a negative impact on the sensing characteristics of air flow rate sensor,and that honeycomb gridiron rectifier can effectively guarantee the accuracy of the wind measurement,which is very beneficial to shorten the length of straight inlet duct before terminals and reduce space requirement in engineering.
机构地区 上海理工大学
出处 《流体机械》 CSCD 北大核心 2011年第1期1-5,共5页 Fluid Machinery
基金 上海市教委重点学科建设项目(J50502)
关键词 变风量系统 末端装置 风量传感器 传感特性 VAV system air terminal device air flow rate sensor sensing characteristics
  • 相关文献

参考文献12

二级参考文献20

  • 1杨国荣,叶大法,胡仰耆,魏炜.变风量末端装置风速传感器的基本原理及其应用[J].暖通空调,2006,36(7):59-64. 被引量:9
  • 2Gil Avery. Building pressure controls to comply with the Americans with disabilities ACT and AHRAE STANDARD 62-1989.1995. AHRAE. Trans. 101 (2) :619-624.
  • 3Douglass C. Hittle. Controlling variable-volume systems. 1999. AHRAE J, 39 (9) : 50-42.
  • 4Glen A. chamberlin,Kevin s. Maki. VAV systems and out door air. 1999. AHRAE J ,40(10) :39-47.
  • 5魏志祥(译),现代隐身飞机,1991年,189页
  • 6王寒栋.制冷空调测控技术[M].北京:机械工业出版社,2003
  • 7TITUS产品样本(1998),美国江森自控公司产品样本,美国皇家空调设备工程有限公司产品样本.
  • 8日本Topre公司产品样本.
  • 9日本Kubota公司产品样本.
  • 10日本SINKO公司产品样本