数据中心机架式服务器选型对其热环境的影响及优化分析 被引量:6

Effect and optimization of rack servers selection in data center on the thermal environment
原文传递
导出
摘要 数据中心热环境是空调系统制冷效果和能量利用的综合体现,其优良受到诸多因素的影响。为研究机架式服务器的选型对数据中心热环境的影响,对三种不同功率的1U服务器的数据中心进行仿真模拟,并分析优化其热环境。结果表明,采用封闭冷通道、增加空U挡板和提高送风温度均能改善机房的热环境,提高冷量利用率。 The thermal environment of data center is a comprehensive reflection of air flow distribution and energy utilization, whose performance is influenced by different factors. Simulation on three 1U rack servers with different powers was carried on to an- alyse the effect of rack servers design on the thermal environment in data center. Measurements results show that these methods such as adding cold aisle enclosure, adding baffles and increasing supply - air temperature can improve the air flow and cooling effect.
出处 《低温与超导》 CAS 北大核心 2016年第8期74-78,共5页 Cryogenics and Superconductivity
基金 国家自然科学基金资助项目"相变微/纳米胶囊对溶液除湿过程热质传递的影响机理研究"(51406076) 江苏省自然科学基金资助项目"相变微/纳米胶囊对溶液除湿和再生性能影响机理研究"(BK20140942)
关键词 数据中心 机架式服务器 热环境 数值模拟 Data center, Rack servers, Thermal environment, Simulation
  • 相关文献

参考文献8

  • 1云计算发展与政策论坛.数据中心能效测评指南[C].2012.
  • 2高彩凤,于震,吴剑林.典型数据机房热环境分析及气流组织优化[J].暖通空调,2013,43(9):101-106. 被引量:38
  • 3蒋雅靖,刘刚.数据机房不同下送风方式的模拟分析及对比[J].建筑节能,2011,39(1):18-20. 被引量:14
  • 4Cho J, Yang J ,Park W,et al. Evaluation of air distribu-tion system ’ s airflow performance for cooling energy sav-ings in high - densitty data centers [ J ]. Energy andBuilings, 2014,68:270 -279.
  • 5Srinarayana N,Fakhim B ,Behnia M ,et al. Thermal per-formance of an air - cold data center with raised - floorand non - raised - floor configurations [ J ]. Hear transferEngineering, 2014,35 (4):384 -397.
  • 6沈月明.探讨计算机机房节能[J].电子世界,2014(14):133-134. 被引量:1
  • 7ASHRAE TC 9.9,2011, Thermal Guidelines for DataProcessing Environments [ S]. Atlanta, GA.
  • 8Wang L,SU Khan. Review of performance metrics forgreen data centers : a taxonomy study [ J ]. The Journal ofSuper computing, 2013 ,63 :639 -656.

二级参考文献11

  • 1赖世能,侯福平,宗凌.IDC机房空调电源技术专题系列之一:IDC机房上下送风方式空调系统分析比较[J].电信技术,2005(11):33-35. 被引量:14
  • 2王金.3G网络拒绝重复建设[N].通信产业报,2006-04-20.
  • 3中国电子工程设计院.GB50174-2008电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
  • 4云计算发展与政策论坛.数据中心能效测评指南[C].2012.
  • 5Environmental Protection Agency. Report to congress on server and data center energy efficiency [-R. Public Law 109-431. U S, 2007.
  • 6Sun H S, Lee S E. Case study of data centers' energy performance[J. Energy and Buildings, 2006,38 (5) . 522-533.
  • 7Koomy J G. Growth in data center electricity use 2005 to 2010 EEB/OL. E2011 http: /// www. analyticspress, eom/datacenters, html.
  • 8ASHRAE. ASHRAE TC 9.9 Thermal guidelines for data processing environments expanded data center classes and usage guidanceES, 2011.
  • 9Sharma R K, Bash C E, Patel R D. I)imensionless parameters for evaluation of thermal design and performance of large-scale data centersC// In 8th ASME/AIAA Joint Thermophysies and Heat Transfer Conference, 2002.
  • 10Herrlin M. Rack cooling effectiveness in data centers and teleeom central offices the rack cooling index (RCI)EGT// ASHRAE Trans, 2005,111(2) : 1 -11.

共引文献51

同被引文献40

引证文献6

二级引证文献29

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部