期刊文献+

锅炉低温再热器内壁腐蚀原因分析及预防措施 被引量:3

Reason analysis and prevention measures of inner wall corrosion of a boiler low-temperature reheater
下载PDF
导出
摘要 某电厂330 MW亚临界锅炉由于屏式再热器、墙式再热器内壁腐蚀而发生2次泄漏事故。结合现场割管检查、沉积物检测、金相及机械性能分析报告,从化学水处理和启、停炉运行操作等方面入手,分析了低温再热器产生腐蚀的原因,提出了现场处理方案和针对性防腐措施。 For the 330 MW subcritical boiler of a certain power plant,two leakage accidents occurred due to the inner wall corrosion of platen reheater and wall type reheater. Combining with the tube cutting inspection on site,sediment test and analysis reports of metallographic and mechanical properties,this paper analyzed the corrosion reason of low-temperature reheater from the aspects of chemical water treatment,operations of boiler startup and shutdown,etc. After that,it proposed the treatment scheme on site and corresponding anti-corrosion measurements.
出处 《华电技术》 CAS 2017年第8期32-35,共4页 HUADIAN TECHNOLOGY
关键词 亚临界锅炉 低温再热器 内壁腐蚀 泄漏 subcritical boiler low-temperature reheater inner wall corrosion leakage