Analysis of a Water-Cooled Unit under Different Loads

下载PDF
导出
摘要 In order to ensure the safe operation of the compressors used in water chillers,in the present study some interlock protections have been added to the related design.These include a low pressure protection,a high pressure protection,an exhaust temperature protection and a differential pressure protection.Some tests have been conducted by tuning the saturation suction and exhaust temperatures of the compressor through adjustment of the cold source outlet temperature and the ambient temperature.The results show that the ambient temperature increases with decreasing device load and increasing fan speed under the same saturated suction temperature;the device refrigerating capacity steps up with augmenting load and dropping saturation exhaust temperature,while it is not greatly affected by the fan speed.Moreover,the Energy efficiency ratio(COP)decreases with the rise of the saturation exhaust temperature.This parameter is not affected much by the device load and fan speed at high saturation exhaust temperature,while it improves on increasing the device load and decreasing the fan speed at low saturation exhaust temperature.
出处 《Fluid Dynamics & Materials Processing》 EI 2023年第7期1863-1873,共11页 流体力学与材料加工(英文)