摘要 Data centers are recognized as one of the most important aspects of the fourth industrial revolution since conventional data centers are inefficient and have dependency on high energy consumption,in which the cooling is responsible for 40%of the usage.Therefore,this research proposes the immersion cooling method to solving the high energy consumption of data centers by cooling its component using two types of dielectric fluids.Four stages of experimentalmethods are used,such as fluid types,cooling effectiveness,optimization,and durability.Furthermore,benchmark software is used to measure the CPU maximum work with the temperature data performed for 24 h.The results of this study show that the immersion cooling reduces 13℃ lower temperature than the conventional cooling method which means it saves more energy consumption in the data center.The most optimum variable used to decrease the temperature is 1.5 lpm of flow rate and 800 rpm of fan rotation.Furthermore,the cooling performance of the dielectric fluids shows that the mineral oil(MO)is better than the virgin coconut oil(VCO).In durability experiment,there are no components damage after five months immersed in the fluid.
出处 《Energy Engineering》 EI 2022年第1期275-286,共12页 能源工程(英文)
基金 This work is financially supported by the Ministry of Research and Technology of Indonesia(BRIN)in the project called“Penggunaan Immersion Cooling untukMeningkatkan Efisiensi Energi Data Center”.