摘要
阐述500kV变电站内35kV站用变保护装置与控制电源的配置,在任何一路直流电源失电的情况下,存在站用变保护装置都无法跳开断路器的隐患,提出两种相应的改进措施。
This paper describes the configuration of the 35kV station transformer protection device and control power supply in a 500kV substation.In the event of any DC power loss,there is a hidden danger that the station transformer protection device cannot trip the circuit breaker.Two corresponding improvement measures are proposed.
作者
徐佳赟
杨岚沛
封永才
王鑫
达慧
马宇辉
侯可
陈怡霏
XU Jiayun;YANG Lanpei;FENG Yongcai;WANG Xin;DA Hui;MA Yuhui;HOU Ke;CHEN Yifei(State Grid Henan Electric Power Company Ultra High Voltage Company,Henan 450100,China)
出处
《集成电路应用》
2023年第10期294-295,共2页
Application of IC
关键词
直流电源
站用变保护
二次回路
可靠性
DC power supply
station transformer protection
secondary circuit
reliability.