期刊文献+

岐伯山医院排水系统设计总结与思考

Summary and thinking of drainage system design of Qiboshan Hospital
下载PDF
导出
摘要 详细介绍了郑州岐伯山医院排水系统及污水处理站的设计要点,并结合国家相关规范及标准探讨了应急临时传染病医院排水系统设计中应注意的经验和教训。提出了初期雨水建议统一收集消毒处理后排至市政污水管网,后期雨水收集后直接排至市政雨水管网;传染病医院生活排水系统的通气管道采用紫外线消毒器进行消毒处理;传染病医院污水进污水处理站之前经历两次预消毒,可以最大程度的保证整个污水处理系统消毒措施的安全性;传染病医院污水处理站应设计污水连续在线监测系统,采用无人值守,杜绝工作人员感染病毒的可能性。 This paper introduces the design points of the drainage system and sewage treatment station of Qiboshan Hospital in Zhengzhou,and discusses the experience and lessons that should be paid attention to in the design of the drainage system of emergency temporary infectious disease hospital according to the relevant national norms and standards.It is suggested that the rainwater in the initial stage should be collected,disinfected and discharged to the municipal sewage pipe network,and the rainwater in the later stage should be directly discharged to the municipal sewage pipe network.The ventilation pipe of the domestic drainage system in infectious disease hospital is disinfected by ultraviolet disinfector.The hospital sewage of infectious diseases should be pre-disinfected twice before entering the sewage treatment station,which can ensure the safety of the disinfection measures of the whole sewage treatment system to the greatest extent.The sewage treatment station of infectious disease hospital should design sewage continuous online monitoring system,adopt unattended,and eliminate the possibility of infection of staff.
作者 孙宏伟 张坡 张伟光 刘占礼 解云飞 SUN Hongwei;ZHANG Po;ZHANG Weiguang;LIU Zhanli;XIE Yunfei(CSCEC Zhongyuan Architectural Design Institute Co.,Ltd.,Zhengzhou 450000,China)
出处 《给水排水》 CSCD 北大核心 2022年第S01期964-968,974,共6页 Water & Wastewater Engineering
关键词 传染病医院 医院污水 初期雨水径流 紫外线消毒 二级处理 MBR Infectious diseases hospital Hospital sewage Initial rainfall runoff Ultraviolet disinfection Secondary treatment MBR
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部