期刊文献+

密肋槽钢修复薄钢板剪力墙抗震性能研究 被引量:4

Seismic behavior of thin steel plate shear wall repaired by multi-ribbed channel grid
原文传递
导出
摘要 薄钢板剪力墙的屈曲荷载低,在地震作用下会产生较大残余变形,影响二次抗震性能。为此提出锚固密肋槽钢的方法修复震后损伤钢板剪力墙,根据附加肋板的受力模型,推导了修复内嵌钢板所需肋条间距限值公式。为研究该公式的合理性及修复后结构的抗震性能,对一榀单跨双层薄钢板剪力墙施加了两阶段低周往复荷载,即第Ⅰ阶段加载至1/130位移角,以达到在该加载步模拟地震损伤的目的,之后安装密肋槽钢修复内嵌钢板;第Ⅱ阶段将修复加固后结构加载至破坏,研究其抗震性能变化。结果表明:加劲肋具有足够刚度,可以有效抑制内嵌钢板残余变形;修复后结构破坏模式合理,滞回曲线饱满,附加肋板可以有效提高其耗能能力;结构刚度及延性较高,刚度相较原结构提升14%,位移延性系数达到3.12,具有良好的变形能力。 The buckling strength of thin steel plate shear wall is low.Therefore,earthquakes will produce residual deformation to the embedded steel plate,which affects the post-earthquake performance of the structure.The method of anchoring multi-ribbed channel grid to repair the damaged steel plate shear wall was proposed.The size limit of the multi-ribbed grid was derived according to the stress model of the additional ribs.To identify the rationality of the proposed approach and to study the performance of the repaired structure,a single-span,two-story experimental specimen was tested under low cycle reversed loading by two steps.In stepⅠ,the specimen was first loaded to the maximum inter-story displacement angle of 1/130 to simulate earthquake damage.Then the specimen was repaired.In stageⅡ,the repaired structure was loaded to damage.The test result shows that the multi-ribbed grid is rigid enough to suppress the residual deformation of the embedded steel plate.The repaired structure has a reasonable failure mode.The hysteresis loop is plump,and the additional ribs effectively increase its energy dissipation.The stiffness and ductility of the structure are satisfactory.The stiffness of the repaired structure is 14%higher than that of the original one.The ductility coefficient reaches 3.12,which means the structure has a good deformation capability.
作者 杜一鹏 郝际平 于金光 房晨 葛明兰 DU Yipeng;HAO Jiping;YU Jinguang;FANG Chen;GE Minglan(School of Civil Engineering,Xi’an University of Architecture&Technology,Xi’an 710055,China)
出处 《建筑结构学报》 EI CAS CSCD 北大核心 2020年第3期44-52,共9页 Journal of Building Structures
基金 国家自然科学基金项目(51578442) 国家重点研发计划(2016YFC0701201).
关键词 钢板剪力墙 密肋槽钢 拟静力试验 修复后抗震性能 steel plate shear wall multi-ribbed channel grid pseudo-static test post-repair seismic performance
  • 相关文献

参考文献11

二级参考文献167

共引文献196

同被引文献40

引证文献4

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部