Analysis on Coil Spring Fracture of Substation Circuit Breaker
下载PDF
导出
摘要 某500 kV变电站断路器卷簧发生断裂,通过磁粉检测、渗透检测、光谱分析、硬度测量、拉力试验、脱碳层检测、金相检验、断口分析等,分析结果表明原始裂纹为卷簧断裂所致。 The coil spring of a circuit breaker in a certain 500 kV transformer substation is fractured.A series of detections and analyses have been made such as magnetic testing(MT),penetrant testing(PT),spectral analysis,hardness measurement,tensile test,decarburization layer detection,metallographic examination,fracture analysis,etc..The result shows that the original crack is caused by coil spring fracture.
作者 叶建锋 熊宇 田泽 梅云平 沈祎侬 YE Jianfeng;XIONG Yu;TIAN Ze;MEI Yunping;SHEN Yinong(Electric Power Research Institute,State Grid Hubei Electric Power Co.,Ltd.,Wuhan Hubei 430077,China;Hubei Fangyuan Dongli Electric Power Science&Research Co.,Ltd.,Wuhan Hubei 430077,China)
出处 《湖北电力》 2020年第1期80-84,共5页 Hubei Electric Power
基金 运维专项成本项目(项目编号:B3153218002100T00000003)
关键词 变电站 断路器 卷簧 磁粉检测 光谱分析 transformer substation circuit breaker coil spring magnetic testing spectral analysis