摘要
以深圳某三甲综合医院住院部作为研究对象,选用中国标准年(CSWD)气象数据,采用全年负荷计算及能耗分析软件,以《非供暖季不同末端空调系统综合能耗的计算分析方法浅析》的分析方法针对两种空调系统形式下的非供暖季系统综合能耗进行分析计算,以得出能耗相对最优空调形式。结果表明,温湿度独立控制系统相比常规热湿耦合系统综合能耗节能26.4%,并针对极端情况下的结露现象提出相应解决措施。
Taking the inpatient department of a third-class general hospital in Shenzhen as the research object,the meteorological data of China standard year(CSWD)is selected,and the annual load calculation and energy consumption analysis software is used.The analysis method"analysis method of calculation and analysis of comprehensive energy consumption of different terminal air conditioning systems in non heating season"aims at the comprehensive energy consumption of two types of air conditioning systems in non heating season.Through analysis and calculation,we can get the relative optimal air conditioning form of energy consumption.The results show that the integrated energy consumption of the temperature and humidity independent control system is 26.4%less than that of the conventional heat and humidity coupling system,and the corresponding solutions to the condensation phenomenon in extreme cases are proposed.
作者
王思叶
于振峰
赵伟
WANG Si-ye;YU Zhen-feng;ZHAO Wei(Shenzhen Huayang International Engineering Design Co.,Ltd,Shenzhen 518000,Guangdong,China)
出处
《建筑节能》
CAS
2020年第8期86-90,共5页
BUILDING ENERGY EFFICIENCY
关键词
医疗建筑
热湿耦合
空调形式
综合能耗
medical building
heat moisture decoupling
air conditioning form
comprehensive energy consumption