摘要
介绍了一起检查测量变压器有载分接开关隐蔽故障的实例,此例表明:在分析变压器绕组直流电阻测量结果时,除了考察直流电阻不平衡率外,还应当考察每相绕组各相邻档之间电阻的差值分布是否均匀,以便确认有载分接开关是否存在故障。
A living example about removing the hidden fault of the onload tap-changing switch of a measuring transformer is described;the example shows that when analyzing the measured result of DC resistance in the transformer windings,except the unbalance ratio of DC resistance should be examined;the distribution difference of DC resistance between neighbour resistance grades of every phase should be examined also to ascertain the on-load tap-changing switch whether or not exists fault.
出处
《湖北水力发电》
2008年第1期41-44,共4页
Hubei Water Power
关键词
变压器
直流电阻
不平衡率
有载分接开关
故障
transformer
DC resistance
unbalance ratio
on-load tap-changing switch
fault