自然作用压力对分户循环热水供暖系统的影响

The effect of circulating force on individual circulating heating system
下载PDF
导出
摘要 通过实际工况下分户循环系统自然作用压力的分析计算得出 :实际运行时的供水温度越高、供回水温差越大 ,越适合选用异程式系统 ;反之 ,越适合选用同程式系统。提出异程式系统可通过在设计时减小比摩阻的方法来减小垂直失调 ; By analyzing the circulating force of individual circulating system under the circumstance of actual mode, the author concludes that the higher the temperature of supply water is and the bigger the temperature difference between the supply water and the return water is, the more suitable it is for direct return hot water heating system to be used; otherwise, it is more suitable for reversed return hot water heating system to be used. Direct return hot water heating system can reduce vertical thermal disorder by reducing specific frictional resistance during design; whereas reversed return hot water heating system can reduce vertical thermal disorder by adding the partial resistance of the upper circulation.
出处 《长春工程学院学报(自然科学版)》 2002年第4期44-46,共3页 Journal of Changchun Institute of Technology:Natural Sciences Edition
关键词 自然作用压力 分户循环 热水供暖系统 实际运行工况 垂直失调 circulating force individual circulating system hot water heating system actual operating mode vertical thermal disorder