大型发电机中性点配电变压器电阻接地选型设计 被引量:10

Lectotype and Design of Neutral Grounding Transformer and Load Resistor for Large-sized Generator
下载PDF
导出
摘要 当前大型发电机越来越多地采用中性点经配电变压器电阻接地的接地方式,并装设通过中性点接地变压器注入低频信号的外加电源式100%定子接地保护.通过分析计算注入信号与发电机中性点接地变压器参数之间的数值关系,认为接地变压器负载电阻二次值不宜太小,应当合理选择接地变压器电压变比,适当提高接地变压器二次侧额定电压,从而可适当增大注入电压信号,并增大保护装置检测的低频电压、低频电流分量,提高保护的可靠性和灵敏度.
出处 《中国电机工程学报》 EI CSCD 北大核心 2007年第z1期89-93,共5页 Proceedings of the CSEE
  • 相关文献

参考文献3

  • 1[1]Power System Relaying Committee of the IEEE Power Engineering Society.IEEE C37.101-1985 IEEE guide for generator ground protection[S].New York:IEEE,Inc,1985.
  • 2[2]Power System Relaying Committee of the IEEE Power Engineering Society.IEEE C37.102-1995 IEEE guide for AC generator protection[S].New York:IEEE,Inc,1996.
  • 3[8]Brown PG,Johnson I B,Stevenson J R.Generator neutral grounding,some aspects of application for distribution transformer with secondary resistor and resonant types[J].IEEE Transaction on Power Apparatus and Systems,1978,97(3):683-694.