期刊文献+

圆形管道风速测定与校正方法实验 被引量:31

Experimental study on determination and correction method of wind speed in circular pipe
下载PDF
导出
摘要 针对通常所用的风速传感器只能监测某一点的风速,不能准确监测断面平均风速的问题,采用实验室研究测试和数值分析的方法,对圆形断面风速分布进行研究.根据断面中垂线上18个点的实测风速值,得出通过中垂线上某一点风速求该断面平均风速的校正系数.经验证,利用该风速校正系数能得出较为精确的断面平均风速值,为风速传感器的校正提供了一种技术途径. Currently the wind sensor commonly used can only monitor the wind speed at one point,not the average wind speed at a cross-section.In order to overcome this problem,this paper investigates the wind speed distribution at a round section using the methods of laboratory test and numerical analysis.Based on the measured wind speeds at 18 points in the perpendicular bisector of a section,the correction coefficients for calculating average wind speed at the section using the wind speed at one point have been obtained.The study shows that a more accurate average wind speed at a cross-section can be obtained by using wind speed calibration coefficients.The study provides a technical mean for wind sensor calibration.
出处 《辽宁工程技术大学学报(自然科学版)》 CAS 北大核心 2012年第6期801-804,共4页 Journal of Liaoning Technical University (Natural Science)
基金 辽宁省自然科学基金资助项目(20092199) 辽宁省教育厅基金资助项目(20060389)
关键词 圆形管道 风速分布 皮托管 速压 校正系数 风速传感器 风量监测 线性关系 circular pipe wind speed distribution pitot tube velocity pressure correction coefficient wind sensor blast monitoring linear relationship