通信基站用溶液循环式换热机组的实验研究

Experiment on Free Cooling Unit for a Telecommunication Base Station
下载PDF
导出
摘要 在通信基站的能耗中,空调能耗占据了40%左右,为了降低通信基站空调能耗,设计出利用自然冷源的溶液循环式换热机组,以降低空调能耗,并对样机进行了实验测试。结果表明,在实验工况范围内,运行稳定,换热效果良好。换热器的温度效率可达45%,传热系数可达60 W/(m^2·℃)。 The power consumption of air conditioning for a telecommunication base station(TBS) in China occupies almost 40%of the total power consumption.In order to reduce the power consumption,a free cooling unit with working fluid of glycol-water unit was designed for the base station to share the cooling load with the air conditioning,and the prototype also have been tested.The results indicate that the free cooling unit works well with a good heat dissipation performance under the testing conditions.The temperature efficiency of the unit can reach 45%and the heat transfer coefficient reaches 60 W/(m^2·℃)。
出处 《制冷技术》 2012年第3期31-34,45,共5页 Chinese Journal of Refrigeration Technology
关键词 通信基站 节能 溶液循环式换热机组 Telecommunication base station Energy saving Free cooling unit
  • 相关文献

参考文献6

二级参考文献28

  • 1殷平.新型板式全热交换器研制——经济分析[J].暖通空调,2006,36(3):53-58. 被引量:14
  • 2侯福平.通信机房空调系统节能技术探讨[J].电信技术,2006(6):20-21. 被引量:24
  • 3赵晓峰.自然冷源制冷在通信机房试验与应用[EB/OL].[2007-11-22].http://www.corncw.cn/.
  • 4中国电信[2005]741号.中国电信数据中心机房电源、空调环境设计规范(暂行).2005.
  • 5王世超,郭轶.综合通信楼IDC机房空调系统改造[EB/OL].[2007-11-22].http://www.comcw.cn/.
  • 6JONATHAN G K. Estimating total power consumption by servers in the U. S. and the world [R]. 2007.
  • 7VINCENT M. Preventing [ EB/OL ]. [ 2009-3-9 ]. a data center power crisi http ://searchdatacenter techtarget, com/tip/0, 289483, sid80- gci1350324 mem1,00, html.
  • 8IYENGAR M, SCHMIDT R. Analytical modeling for thermodynamic characterization o[ data center cooling systems[J].Journal of Electronic Packaging, 2009, 131(2) : 1-9.
  • 9CHANDRAKANT D P, CULLEN E B, CHRISTIAN B, et al. Computational fluid dynamic modeling of high compute density data centers to assure system inlet air specifications [C]//Proceedings of IPACK ' 01, The Pacific Rim/ASME International Electronic Packaging Technical Conference and Exhibition, Kauai, Hawaii, USA, July, 2001. IPACK2001-15622.
  • 10MALONE CG, VINSON W, BASH CE. Data center TCO benefits of reduced system airflow [C]// Proceedings of 11 th Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, Orlando, FL, May 28-31, 2008. New York: IEEE, 2008: 1199-1202.

共引文献39

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部