某机场新建航站楼集中空调通风系统竣工验收卫生学评价 被引量:5

Hygienic Evaluation for Final Acceptance of Central Air Conditioning Ventilation System in New Airport Terminal
下载PDF
导出
摘要 目的分析集中空调通风系统中可能存在的健康危害因素,减少空气传播性疾病在建筑物内爆发流行的潜在危险。方法采用查看设计图、现场调查、现场采样检测、风险评估等方法对该建筑物的集中空调通风系统进行调查、分析和评价。结果该建筑物集中空调通风系统风管内表面有3个采样点的细菌总数和9个采样点的真菌总数超过标准限值;送风有2个采样点的细菌总数和9个采样点的真菌总数超过标准限值;其余检测指标合格。结论该集中空调通风系统不符合《公共场所集中空调通风系统卫生规范》(WS 394-2012)的要求,须经过清洗消毒合格后方可投入使用。 Objectives To identify and analyze the health risk factors which might present in the central air conditioning ventilation system( CACVS) of a new airport terminal to reduce the potential risk of airborne disease outbreak. Methods To investigate,analyze and evaluate the acceptance of the system through checking the design,field investigation,field sampling and detection,risk assessment etc. Results The total bacteria counts and the total fungi counts on the inner surface of air tubes exceeded the national standard in 3 samples and 9 samples,respectively.The total bacteria counts and the fungi counts in air supply system exceeded the national standard limits in 2 samples and in 9 samples,respectively. The other indexes were qualified. Conclusions This CACVS was not qualified for the requirement in Hygienic Specification of Central Air Conditioning Ventilation System in Public Buildings( WS 394-2012). Therefore,this CACVS could be used only after being cleaned and disinfected.
出处 《环境卫生学杂志》 北大核心 2014年第3期262-265,268,共5页 JOURNAL OF ENVIRONMENTAL HYGIENE
关键词 机场 公共场所 集中空调通风系统 危险因素 卫生学评价 airport the central air conditioning ventilation system risk factors hygiene evaluation
  • 相关文献

参考文献7

二级参考文献21

共引文献22

同被引文献28

引证文献5

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部