摘要
针对含有测量时滞的线性时滞系统,研究其执行器发生频率已知但幅值和初始相位未知的正弦故障时的故障诊断方法.提出了一种基于观测器的故障诊断方法,该方法首先通过建立故障的状态空间模型,将执行器故障的动态特性表示出来;然后利用一种测量时滞的无时滞转换方法,将时滞系统转换成无时滞系统;最后通过构造一种新颖的状态观测器,设计了不利用残差体现故障的故障诊断器,实现了系统执行器故障的在线诊断.仿真实例验证了该方法的可行性和有效性.
The approaches to fault diagnosis were researched for linear time-delay systems with delayed measurements when sinusoidal faults with known frequencies but unknown amplitudes and initial phases happened to the actuators.A novel observer-based fault diagnosis approach was proposed.This scheme first established the state space model for the actuator faults so that the actuator faults′ dynamic characteristics were described.Then,by utilizing the delay-free transformation approach to the delayed measurements,the system with delayed measurements was transformed into a delay-free one in form.Finally,the fault diagnoser which didn′t need the residual to embody faults was designed by constructing a novel state observer,and the on-line diagnosis was realized for the actuator faults.The feasibility and validity of the proposed scheme was demonstrated by a simulation example.
出处
《华中科技大学学报(自然科学版)》
EI
CAS
CSCD
北大核心
2009年第S1期288-291,296,共5页
Journal of Huazhong University of Science and Technology(Natural Science Edition)
基金
国家自然科学基金资助项目(40776051)
青岛市科技计划资助项目(06-2-2-9-jch)
青岛农业大学高层次人才启动基金资助项目(630815)
关键词
故障诊断
时滞系统
正弦故障
测量时滞
无时滞变换
fault diagnosis
time-delay systems
sinusoidal faults
delayed measurements
delay-free transformation