期刊文献+

Modeling and Assessment of Buoyancy-Driven Stratified Airflow in High-Space Industrial Hall

Modeling and Assessment of Buoyancy-Driven Stratified Airflow in High-Space Industrial Hall
下载PDF
导出
摘要 In industrial environment,heat sources often are contaminant sources and health threatening contaminants are mainly passive,so a detailed understanding of airflow mode can assist in work environment hygiene measurement and prevention.This paper presented a numerical investigation of stratified airflow scenario in a high-space industrial hall with validated commercial code and experimentally acquired boundary conditions.Based upon an actually undergoing engineering project,this study investigated the performance of the buoyancy-driven displacement ventilation in a large welding hall with big components manufactured.The results have demonstrated that stratified airflow sustained by thermal buoyancy provides zoning effect in terms of clean and polluted regions except minor stagnant eddy areas.The competition between negative buoyant jets from displacement radial diffusers and positive buoyant plume from bulk object constitutes the complex transport characteristics under and above stratification interface.Entrainment,downdraft and turbulent eddy motion complicate the upper mixing zone,but the exhaust outlet plays a less important role in the whole field flow.And the corresponding suggestions concerning computational stability and convergence,further improvements in modelling and measurements were given. In industrial environment,heat sources often are contaminant sources and health threatening contaminants are mainly passive,so a detailed understanding of airflow mode can assist in work environment hygiene measurement and prevention.This paper presented a numerical investigation of stratified airflow scenario in a high-space industrial hall with validated commercial code and experimentally acquired boundary conditions.Based upon an actually undergoing engineering project,this study investigated the performance of the buoyancy-driven displacement ventilation in a large welding hall with big components manufactured.The results have demonstrated that stratified airflow sustained by thermal buoyancy provides zoning effect in terms of clean and polluted regions except minor stagnant eddy areas.The competition between negative buoyant jets from displacement radial diffusers and positive buoyant plume from bulk object constitutes the complex transport characteristics under and above stratification interface.Entrainment,downdraft and turbulent eddy motion complicate the upper mixing zone,but the exhaust outlet plays a less important role in the whole field flow.And the corresponding suggestions concerning computational stability and convergence,further improvements in modelling and measurements were given.
出处 《湖南大学学报(自然科学版)》 EI CAS CSCD 北大核心 2009年第S1期19-22,共4页 Journal of Hunan University:Natural Sciences
基金 Supported by the National Natural Science Foundation of China(10775047) Hunan Provincial Natural Science Foundation of China(08JJ3093) the Key Programof Scientific and Technical of Hunan Province(2007FJ2006)
关键词 modelling buoyancy-driven large ENCLOSURE INDUSTRIAL ventilation modelling buoyancy-driven large enclosure industrial ventilation
  • 相关文献

参考文献5

  • 1JELENA S,CHEN Q.An example of verification,validation,and reporting of indoor environment CFDanalyses[].ASHRAE Transactions.2002
  • 2Patankar SV.Numerical Heat Transfer and Fluid Flow[]..1980
  • 3Raimo Niemiela,Hannu Koskela,Kerstin Engstrom.Stratification of Welding Fumes and Grinding Particles in a Large Factory Hall Equipped with displacement ventilation[].Annals of Occupational Hygiene.2001
  • 4Elisabeth Mundt.Displacement ventilation systems-convection flows and temperature gradients[].Building and Environment.1995
  • 5VERSTEEG H K,MALALASEKERA W.An introduction to computational fluid dynamics[]..1996

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部