期刊文献+

某广场空调系统冷冻水大温差的适用性分析 被引量:10

Analysis of Suitability of Large Chilled Water Temperature Difference of Air-Conditioning System of an Emporium
下载PDF
导出
摘要 本文以某大型商业广场实际工程为研究对象,通过对冷冻水系统采用标准温差(7℃/12℃)与大温差(6℃/14℃)两种工况下,冷水机组、冷冻水泵、空调末端的初投资及运行能耗变化趋势的具体分析,提出了冷冻水大温差系统的适用性问题。 The primary investment, energy consumption of chiller, chilled water pump and air handling unit of air-conditioning system of an emporium were discussed under two chilled water difference scheme, i.e., standard temperature difference (7℃/12℃) and large temperature difference (6℃/14℃). The suitability of large temperature difference in chilled water system was studied.
机构地区 广州市设计院
出处 《建筑热能通风空调》 2004年第3期45-47,共3页 Building Energy & Environment
关键词 广场 空调系统 空调末端 冷冻水系统 冷水机组 大温差 建筑能耗 chilled water system, large temperature difference, energy consumption, primary investment, suitability
  • 相关文献

参考文献5

二级参考文献10

  • 1霍小平.关于国外高层办公楼空调水系统大温差设计的探讨[J].暖通空调,1996,26(4):58-60. 被引量:16
  • 2石野裕嗣.关于大温差小流量系统的开发(2)[J].空调暖通技术,1996,4.
  • 3孙格非.上海地区空调冷负荷的频率分布[J].空调暖通技术,1993,4.
  • 4井上宇市 范存养等(译).空气调节手册[M].北京:中国建筑工业出版社,1986..
  • 5彦启森.空调用制冷技术[M].中国建筑工业出版社,1983..
  • 6周祖毅 殷平.上海高层建筑空调设计新方法.空调设计(第二辑)[M].长沙:湖南科技出版社,1998..
  • 7潘雨顺 李玉芝等.中央空调冷水机组运行设计最佳"节能"技术研究[J].流体机械,1999,(8):232-237.
  • 8Wayne Kirsner,P. E. Designing for 42F chilled water supply temperature Does it save energy [J].ASHRAE. Journal January 1998,37~42
  • 9周亚素,陈沛霖.空调冷冻水系统大温差设计的能耗分析[J].建筑热能通风空调,1999,18(2):18-19. 被引量:37
  • 10殷平.空调大温差研究(1):经济分析方法[J].暖通空调,2000,30(4):62-66. 被引量:40