摘要
An arc model in SiO2 current-limiting fuse has been put forward. Through taking into account the comprehensive effects such as: fundamental action process among particles of arc column, geometrical and external circuit characteristics of arc column, physical procedure in arc column and in cathode and anode, and power equilibrium in arc column plasma et al., parameters such as the temperature, length, volumn, pressure, arc voltage, arc current et al. in the arc column can be obtained by the model. In view of the serious nonlinearity and huge difference among parameters in the equation set of the model, via analysis on these equations, two solution methods for the equations of the model have been presented with a basic accordance between calculated results and test results.
An arc model in SiO2 current-limiting fuse has been put forward. Through taking into account the comprehensive effects such as: fundamental action process among particles of arc column, geometrical and external circuit characteristics of arc column, physical procedure in arc column and in cathode and anode, and power equilibrium in arc column plasma et al., parameters such as the temperature, length, volumn, pressure, arc voltage, arc current et al. in the arc column can be obtained by the model. In view of the serious nonlinearity and huge difference among parameters in the equation set of the model, via analysis on these equations, two solution methods for the equations of the model have been presented with a basic accordance between calculated results and test results.