期刊文献+

双曲冷却塔等效静力风荷载规范适应性研究 被引量:10

Adaptability study on a China's code for equivalent static wind load of hyperbolic cooling towers
下载PDF
导出
摘要 针对我国规范关于大型双曲冷却塔等效静力风荷载条文仅适用于高度小于165 m冷却塔、在缺少系统研究情况下只能借鉴国外规范问题,以单塔为例对德国规范等效静力风荷载计算公式进行适当变换,获得与我国规范完全一致的表达形式,且式中只有风振系数与平均风压分布系数取值有差异,对两国规范中两参数的取值进行比较;采用有限元计算方法,对3座不同高度冷却塔在中、德规范等效静风荷载作用下内力及变形分布进行计算分析。结果表明,我国规范关于等效静力风荷载条文规定也适应200 m高的冷却塔。 The equivalent static wind load of large hyperbolic cooling towers with a height over 165m is not provided in codes of China. In absence of systematic research, the relevant provisions from foreign standards were used for reference. Firstly, taking a single tower for an example, some appropriate transformations were made for the formula of the equivalent static wind load from Germany's code to result in an expression entirely consistent with that in China's code, except the discrepancies of the gust loading factor and the mean wind pressure distribution coefficient between two codes. Then, a comparison was made between the two parameters provided with China's code and Germany's code. Secondly, using the finite element method, the wind induced responses of three cooling towers with different heights were calculated under action of different equivalent static wind load obtained according to the Chinese code and the German code, respectively. The results showed that the provisions in China's code about equivalent static wind load are suitable for a 200 m high cooling tower.
出处 《振动与冲击》 EI CSCD 北大核心 2013年第11期100-105,共6页 Journal of Vibration and Shock
关键词 冷却塔 规范 等效静力风荷载 风振系数 风致响应 Aerodynamic loads Cooling Cooling towers Towers Wind effects
  • 相关文献

参考文献7

二级参考文献48

共引文献154

同被引文献67

引证文献10

二级引证文献21

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部