计及雷击电晕时750kV进线开关触头间暂态过电压的研究 被引量:10

Study on Transient Overvoltage between Contacts of Switch in 750 kV Transmission Line Considering Lightning Corona
下载PDF
导出
摘要 750kV线路进线保护段内单相导线遭受雷击时,导线上会出现强烈的电晕,使雷电波发生衰减和变形。基于线路的库-伏特性,并用简单的电路模型来模拟输电线路电晕特性,研究了进线开关在额定电压为600kV的MOA保护下触头间暂态过电压。结果表明,额定电压为600kV的MOA能有效保护进线开关,并且自身能正常工作;电晕使雷电波发生较大的衰减和变形,对开关触头间过电压幅值影响不大。 When the lightning strokes the feed-in section of 750 kV transmission line, there will be strong corona that contributes to the attenuation and distortion of lightning current. It is concerned what corona will do on the transient overvoltage between contacts of switch. On the basis of the Q-V characteristics of transmission lines, in this paper, a simple circuit model is set up and the transient overvoltage between contacts is studied when the switch is under the protection of MOA of 600 kV rated voltage. The result of computation indicates that the switch in 750 kV transmission line can work normally under the protection of the MOA and the corona causes the great attenuation and distortion of lightning current and does little effect on overvoltage between the contacts.
出处 《高压电器》 CAS CSCD 北大核心 2004年第3期167-169,172,共4页 High Voltage Apparatus
关键词 暂态过电压 进线段 电晕 开关触头 衰减和变形 吸收能量 transient overvoltage feed-in section corona switch contact attenuation and distortion energy absorbed
  • 相关文献

参考文献7

  • 1Li Xiao-rong, O P Malik, Zhao Zhi-da. A Practical Mathematical Model of Corona for Calculationof Transients on Transmission Lines[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1 145-1 152 .
  • 2Sandoval Carneiro. Evaluation of Corona and Line Models in Electromagnetic Transients Simulations [J]. IEEE Trans. on Power Delivery, 1991, 6(1): 334-342.
  • 3M A Al-Tai, H S B Elayyan. The Simulation of Surge Corona on Transmission Lines [J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1 360-1 368.
  • 4陈锦清,李端姣,江健武.热备用状态线路断路器雷击事故分析[J].高电压技术,2001,27(5):69-69. 被引量:8
  • 5宋伟新.两起断路器雷击爆炸事故的分析及探讨[J].广东电力,2000,13(5):43-44. 被引量:8
  • 6张伟钹 何金良 高玉明.过电压防护及绝缘配合[M].北京:清华大学出版社,2002..
  • 7GB/T11022-1999.高压开关设备和控制设备标准的共用技术要求[S].[S].,..

二级参考文献1

  • 1DL/T620-1997 交流电气装置过电压保护和绝缘配合

共引文献34

同被引文献83

引证文献10

二级引证文献126

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部