期刊文献+

变浓度容量调节空调系统的机理与试验研究 被引量:2

Theoretical and Experimental Research on Air-Conditioning System with VaryingComposition Using Non-Azeotropic Refrigerant Mixtures
下载PDF
导出
摘要 在分析混合工质单位容积制冷量随组成浓度变化的特性的基础上 ,结合筛选出的工质R2 2 /R1 4 2b和R32 /R1 2 4 ,进行固定工况下变浓度稳态性能对比试验和变工况变浓度调节稳态性能试验 ,测得空调系统在不同浓度下的稳态性能参数 。 On the basis of analyzing the characteristics of changing refrigerating load by means of varying the composition of non-azeotropic mixture and screening the refrigerant mixtures R22/R142b and R32/R124, the testing methods of fixed experience conditions and variable operating conditions have been carried out.The experimental data of the steady state performance have been obtained.It shows that the capacity control can meet the needs of varying refrigerating load with variable working conditions for the non-azeotropic mixtures.
出处 《制冷学报》 CAS CSCD 北大核心 2004年第2期12-16,共5页 Journal of Refrigeration
关键词 混合工质 变浓度稳态性能 容量调节 动态性能 制冷技术 空调系统 Engineering thermophysics, refrigerant mixture, capacity control, dynamic characteristics, testing method
  • 相关文献

参考文献3

  • 1[1]B. Gromoll, H. Gotbier, Continunous control of the heating capacity of heat pumps by means of non-azeotropic mixtures, IIR Commission E2(1985), Trondneim, Norway, 257~263
  • 2[2]H. Kruse, The advantages of non-azeotropic refrigerant mixtures for heat pump application, Int J Refrig, 1981, 4:119~125
  • 3[3]W.D.Cooper, The use of mixed refrigerants in air-to-air heat pumps, ASHRAE Trans, 1982, 88:1159~1169(part I)

同被引文献16

  • 1张丽娜,陈光明,王勤.一种新型变浓度热泵系统的实验研究[J].西安交通大学学报,2007,41(5):553-556. 被引量:5
  • 2H B Vakil. Thermodynamics of heat exchange in refrigeration cycles with non - azeotropic mixtures. Proc of the XIVth Int.Congress of refrigeration, 1983,305 - 316.
  • 3H Kruse. The advartages of non- azeotropic refrigerant mixtures for heat pump application.Int J Refrig, 1981,4.119 - 125.
  • 4H Kruse, M Kuever, U Quast. Theoretical and experimental investigation of advantageous refrigerant mixture applications ASHRAE Trans, 1985:1383 - 1418.
  • 5E A Vineyard. Laboratory testing of a heat pump system using an R13B1/R152a refrigerant mixture. ASHRAE Trans, 1998,94:292 - 303.
  • 6Y Yoshida, S Suzuki, Y. Mukai et al. Development of rectifying circuit with mixed refrigerants.Int J Refrig. 1989,12: 182- 187.
  • 7Parreira EP, Parise JAR. Performance analysis of capacity control devices for heat pump reciprocating compressors [ J ]. Heat Recovery Systems&CHP. ,1993,13(5) :451-461.
  • 8Kim TS,Shin JY, Kim MS. Cycle analysis and heat transfer characteristics of a heat pump using R22/R142b refrigerant mixtures[ J]. Int. J. Refrig. ,1994,17(6) :391-399.
  • 9Kim M, Kim MS, Kim YC. Experimental study on the performance of a heat pump system with refrigerant mixtures' composition change [ J ]. Energy, 2004 ( 29 ) : 1053-1068.
  • 10Osaka SS,Itami YY,Nakatani K. Heat pump with a reservoir storing higher pressure refrigerant of non-azeotropic mixture[ P]. USA patent 4722195,1988.