期刊文献+

转轮法试验中硅橡胶合成绝缘子损坏现象的研究 被引量:24

ANALYSIS ON FAILURES OF SILICON RUBBER COMPOSITE INSULATORS IN TRACKING WHEEL TEST
下载PDF
导出
摘要 转轮法即将成为 IEC 合成绝缘子正式标准中的试验方法。为研究转轮法对硅橡胶合成绝缘子的筛选能力,以及不同试品参数对试验结果的影响,文中对不同成分配方、不同伞型的硅橡胶合成绝缘子进行了交流电压下的转轮法试验,并分析了试验中试品失效的原因,试验结果表明,转轮法对试品的材料性能和设计缺陷都有一定的筛选能力,并能在一定程度上重现合成绝缘子的现场运行情况。此外,试品伞型对试验结果也有一定的影响。 Tracking wheel test will soon be adopted as a formal ageing test of IEC document. To investigate the filter ability of this test method and the affection of parameters of different samples on the test result, the silicon rubber composite insulators with different components and composition and those with different shed shapes were tested by tracking wheel tests energized with AC voltage, the failure reasons of tested samples were also analyzed. The test results show that the tracking wheel test possesses a certain degree of screening ability for the material property and design defects of the samples, and to some extent the on-site operation situation of composite insulators can be revealed. In addition, the shed shape of samples also affects test result to some extent.
出处 《电网技术》 EI CSCD 北大核心 2004年第19期68-71,共4页 Power System Technology
基金 国家杰出青年科学基金资助项目(50025720)。~~
关键词 硅橡胶合成绝缘子 转轮 交流电压 现场运行 IEC 试验结果 失效 Composite materials Composition Data reduction Electric potential Electric power systems Failure analysis
  • 相关文献

参考文献12

  • 1CIGRE WG 22.03. Worldwide service experience with HV composite insulators[R]. Electra, paris, 2000(191): 27-43.
  • 2Oliveira S M, Tourreil C H. Aging of distribution composite insulators under environmental and electrical stresses[J]. IEEE Trans on Power Delivery, 1990, 5(2): 1074-1077.
  • 3Tourreil C, Kuffel J, Vandermaar J D et al. Refinement of the tracking wheel test method for composite insulators[R]. Report for the Canadian Electricity Association, CEA No 004 D 853, Montreal, 1998.
  • 4IEEE std 1024-1988, IEEE recommended practice for specifying distribution composite insulators (suspension type)[S], 1988.
  • 5LWIWG-01(96), Dead-end/suspension composite insulator for overhead distribution lines[S], 1996.
  • 6LWIWG-02(96), Line post composite insulator for overhead distribution lines[S], 1996.
  • 7IEC 62217 Ed. 1(CDV), Polymeric insulators for outdoor and outdoor use with a nominal voltage greater than 1000V - general definitions test methods and acceptance criteria[S], 2004.
  • 8崔江流,宿志一,易辉.我国硅橡胶合成绝缘子的应用与展望[J].中国电力,1999,32(1):38-41. 被引量:141
  • 9关志成,薛家麒,梁曦东.合成绝缘子用于三峡工程超高压输电线路的技术经济分析[J].电网技术,1994,18(3):12-16. 被引量:9
  • 10蒋兴良,孙才新,司马文霞,王进华,张诚,陈国庆.10kV合成绝缘子覆冰交流闪络特性及冰闪过程的研究[J].中国电机工程学报,2002,22(8):58-61. 被引量:87

二级参考文献8

共引文献338

同被引文献239

引证文献24

二级引证文献421