期刊文献+

330kV GIS中投切电抗器的过电压研究 被引量:7

Investigation of Transient Overvoltage Caused by Circuit Breaker Switching Shunt Reactors in 330 kV GIS
下载PDF
导出
摘要 在很多情况下,电抗器直接接在GIS母线上,在GIS中开关操作时会产生VFTO,VFTO以行波的方式通过母线传播到套管,并耦合到GIS外部端子、电抗器及与之相连的设备,对其带来危害。以某330kVGIS为例,利用EMTP计算了GIS中投切电抗器时VFTO的幅值、波形,并分析了各种因素对电抗器端部过电压的影响,以及避雷器对该过电压的抑制作用。 In many cases, reactors are directly connected to the GIS bus, the circuit breaker operation may generate VFTO, which would propagate towards the bushing along the bus in the form of travelling wave, and be coupled to the outside terminals. The reactor as well as the other equipment connected with the reactor may be subjected to the dangerous stress. This paper computes the waveforms and the maximal amplitudes of such case, and analyses the influence factors. The suppression effect of MOA is also discussed.
出处 《高压电器》 CAS CSCD 北大核心 2004年第5期358-360,共3页 High Voltage Apparatus
关键词 电抗器 过电压 EMTP 开关操作 避雷器 行波 母线 VGIS 耦合 波形 gas insulation substation(GIS) reactor very fast transient overvoltage(VFTO)
  • 相关文献

参考文献3

二级参考文献9

  • 1何善庆.GIS中的快速暂态现象[J].高压电器,1995,31(2):41-46. 被引量:52
  • 2施围.GIS绝缘水平的研究与EMTP[J].高压电器,1988,(5).
  • 3施围 李岱.电磁暂态程序--EMTP介绍[J].电力技术,1987,(2).
  • 4张伟钹 高玉明.电力系统过电压与绝缘配合[M].北京:清华大学出版社,1988,12..
  • 5郝逢年.变电站侵入波保护系统的研究.西安交通大学硕士论文[M].,1985..
  • 6范建斌.在微机上计算变压器的暂态电场.西安交通大学硕士论文[M].,1994..
  • 7尹晓芳 王秋生 等.《72.5kV及以上GIS隔离开关开合母线充电电流的要求’简介[J].标准化信息,2000,(3):27-30.
  • 8王晓彤,牛晓民,施围.电磁暂态计算中新的变压器模型[J].西安交通大学学报,1999,33(4):9-12. 被引量:8
  • 9尹晓芳,杨左,曲再文,柳艺.500 kV GIS中隔离开关开合母线充电电流试验[J].高压电器,2000,36(2):31-33. 被引量:7