期刊文献+

GIS中绝缘子附近自由导电微粒无害化研究 被引量:20

Study of Deactivation of Free Conducting Particle near Spacer in GIS
下载PDF
导出
摘要 综述了绝缘子附近的自由导电微粒对GIS绝缘性能的影响,分析了球形自由导电微粒的运动特性。提出了自由导电微粒无害化的重要性,并对微粒无害化方法及其研究前景进行了讨论,着重讨论了锥形电极的采用。 The serious influence of free conducting particle near spacer on insulation performance in GIS is summarized and the importance of particle deactivation is described in this paper. The behavior of spherical conducting particle is analyzed. The methods of deactivation and the future of deactivation research are also discussed. And some proposals are made emphasizing on the application of cone-shape electrode as particle driver in GIS.
出处 《高压电器》 CAS CSCD 北大核心 2004年第5期370-372,共3页 High Voltage Apparatus
关键词 绝缘子 导电 绝缘性能 电极 球形 GIS 运动特性 微粒 锥形 研究前景 spacer free conducting particle deactivation
  • 相关文献

参考文献19

  • 1T Hattori, M Honda, H Aoyagi. et al. A Study on Effects of Conducting Particles in SF6 Gas and Test Methods for GIS [J]. IEEE Trans. PWRD, 1988, 3(1): 197-204.
  • 2T Yamagiwa. Particle-initiated Breakdown Characteristics on a Ribbed Spacer Surface for SF6 Gas Insulated Switchgear[J].IEEE Trans. PWRD, 1988, 3(3): 954-960.
  • 3Y Khan, K Sakai, M Hara, et al. Importance of the Consideration of Electrical Gradient Force in the Deactivation of Free Conducting Particle under DC Voltage[A]. Proc IEEE Power Eng Soc Trans. Distrib Conf [C], Yokahama, Japan,2002.
  • 4R M Radwan, R Morsi, M A Abd-Allah. Motion of Free Conducting Particles in SF6 Insulated Systems under DC Switching Voltages[J]. IEEE Trans. DEI, 1994, 1(1): 25-29.
  • 5S Yanabu, H Okubo, S Matsumoto, et al. Metallic Particle Motion in 3-phase SF6 Gas Insulated Bus [J]. IEEE Trans. PWRD, 1987, PWRD-2(1): 101-106.
  • 6Y Khan, K Sakai, M Hara, et al. Motion Behavior and Deactivation Method of Free-conduction Particle around Spacer between Diverging Conducting Plates under DC Voltage in Atmospheric Air[J]. IEEE Trans. DEI, 2003, 10(3): 444-457.
  • 7K Sakai, D L Abella, M Hara, et al. Experimental Studies of Free Conducting Wire Particle Behavior between Non-parallel Plane Electrodes with AC Voltages in Air [J].IEEE Trans. DEI, 2003, 10(3): 418-424.
  • 8S Dale, M Hopkins. Methods of Particle Control in SF6 Insulated CGIT System [J]. IEEE Trans. PAS, 1982, PAS101(6): 1654-1661.
  • 9M M Morcos, K D Srivastava. On Electrostatic Trapping of Particle Contamination in GITL Systems [J]. IEEE Trans.PWRD, 1992, 7(4):1 698-1 702.
  • 10T Hasegawa, K Yamaji, M Hatano. Development of Insulation Structure and Enhancement of Insulation Reliability of 500 kV DC GIS[J]. IEEE Trans. PWRD, 1997, 12(1): 194-202.