期刊文献+

基于风粉监测的四角燃烧煤粉炉内温度场 的动态仿真模型研究 被引量:1

A METHOD OF DYNAMIC SIMULATION FOR TEMPERATURE PROFILE IN A FOUR-CORNER FIRED BOILER BASED ON ON-LINE MONITORING OFAIR AND COAL
下载PDF
导出
摘要 针对四角燃烧煤粉炉内温度场有效监测方法的不足,提出了燃烧工况二重数值仿真思想,即在对炉内燃烧状况的离线数值模拟的基础上,通过建立炉内温度场的动态仿真数学模型,从而实现温度场的动态显示,达到对炉内燃烧状况进行监测的目的。应用某热电厂 DG130? 9.8/540 型高压煤粉炉的实际运行数据对计算模型进行了检验,结果表明:温度值的最大误差不超过 12%,说明本文提出的二重仿真理论是可靠的,基本上能满足工业应用的需要。以此为基础,开发了一套燃烧监测与诊断系统,经工业现场应用,达到了预期效果。 Considering the temperature distribution in tangential fired pulverized coal boiler is difficult to be measured and monitored, two-stage numerical simulation was put forward. First, multi-field coupling simulation for a lot of typical work conditions was carried out off-line with the software CFX-4.3, and then an expression of temperature varying with operating parameter was obtained. According to real-time operating parameters, the temperature in arbitrary point of the furnace can be calculated by using this expression. Thus temperature profile can be shown on-line and monitoring for combusting state in the furnace is realized. The simulating model was checked by the parameters measured in a operating boiler, DG130-9.8/540, and the maximum of relative error is less than 12% (maximum of absolute error is less than 120℃),which show that two-stage simulation method is reliable and able to satisfy the requirement of industrial application. Based on this method, a combustion monitoring system had been developed and applied successfully in the thermal power plant.
出处 《中国电机工程学报》 EI CSCD 北大核心 2004年第10期224-227,共4页 Proceedings of the CSEE
关键词 炉内温度 煤粉炉 燃烧状况 风粉 燃烧工况 动态仿真模型 DG 热电厂 离线 诊断系统 Thermal power engineering Pulverized coal boiler Combustion monitoring Temperature monitoring Numerical simulation Dynamic simulation
  • 相关文献

参考文献9

二级参考文献35

共引文献167

同被引文献15

引证文献1

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部