循环冷却水系统无垢低腐蚀率的技术改进 被引量:3

TECHNICAL MODIFICATION FOR THE LOWEST CORROSION RATE AND NON-SCALING CONDITION OF THE RECYCLE COOLNG WATER SYSTEM
下载PDF
导出
摘要 泸天化公司大氮肥循环冷却水系统投用以来,经优选水稳剂配方、改进加氯方式、增设旁滤池、提高补充水质量等措施,年腐蚀率从0.3366mm降至0.0241mm,换热器运行一年无结垢现象。 Since the recycle cooling water system of the large-sized fertilizer plant of Luzhou Natu- ral Gas Chemical Industrial Corporation was put into service, he annual corrosion rate has been dropped from 0.3366mm/a to 0.0241 mm/a and no scaling has been found in heat exchangers after one years operation by means of optimizing the reasonable formula of water quality stablizer,improv- ing the ways of chlorine charging,adding a side filtration pond and improve the quality of make-up water,etc.
出处 《大氮肥》 1995年第6期448-450,共3页 Large Scale Nitrogenous Fertilizer Industry
关键词 循环冷却水系统 大氮肥 水质稳定剂 腐蚀 技术改进 换热器 配方 recycle cooling water,water quality stabilizer,technical modifition,corrosion