期刊文献+

一种超高压输电线路自适应分相电流差动保护新原理研究 被引量:9

Study on new principle of adaptive current differential protection for EHV transmission line
下载PDF
导出
摘要 根据分相电流差动保护的基本判据,分析线路两端电流量幅值和相位对保护动作特性的影响,提出一种制动系数自适应于线路两端电流量幅值之比的分相电流差动保护新原理。按照穿越性电流对差动保护进行制动的传统方法忽略了线路两端电流量幅值之比对保护动作特性的影响,新原理则充分考虑了这一影响。理论分析和动模试验数据表明,采用该新原理可以增加分相电流差动保护抗电流互感器饱和能力,有效提高保护反映区内、外故障的总体性能。 According to the basic criteria,the influence of the amplitude and phase of terminal currents on the sensitivity and reliability of conventional phase-segregated current differential protection is analyzed. A new principle of phase - segregated current differential protection is put forward. It has adaptive restraint coefficient corresponding to the amplitude ratio of terminal currents,which is neglected in the conventional approach with the restraint current derived from the current through the line. The results of theoretical analysis and dynamic simulation tests show that the ability against the influence of CT saturation is improved and its general performance in response to both internal and external faults of the protected transmission line is effectively enhanced.
出处 《电力自动化设备》 EI CSCD 北大核心 2004年第12期12-15,共4页 Electric Power Automation Equipment
关键词 输电线路 电流差动保护 电流互感器饱和 自适应 分相 transmission line current differential protection CT saturation adaptive phase-segregated
  • 相关文献

参考文献10

二级参考文献39

共引文献151

同被引文献94

引证文献9

二级引证文献28

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部