给粉机变频器跳闸引发锅炉MFT动作原因分析及对策 被引量:3

Reason analysis and its countermeasures of boiler main fuel trip caused by frequency converter trip of pulverized coal feeder
下载PDF
导出
摘要 阐述了国电双鸭山发电有限公司1号机组在DCS系统改造后,给粉电源切换过程中,给粉机变频器失去控制指令,造成给粉机跳闸,锅炉燃烧不稳,引发锅炉MFT动作的原因,介绍了严密、有效的改进措施。 The main reasons why the main fuel trip (MFT) took action during the switchover of pulverized coal feeding power source after DCS of No. 1 unit in Shuangyashan generating power Co. Ltd was modified are analyzed in the paper. The results showed that the frequency converter of pulverized coal feeder did not work against control command, which caused pulverized coal feeder to trip, made boiler combustion unsteady and had boiler MFT take action. The close, effective modified measures focusing on the problems described above were also made, and what is more, an excellent effectiveness has been resulted from them.
作者 杜凤叶
出处 《黑龙江电力》 CAS 2004年第6期464-466,共3页 Heilongjiang Electric Power
关键词 给粉机控制 锅炉MFT 变频器控制 pulverized coal feeder control boiler main fuel trip frequency converter control