期刊文献+

SF_6断路器在北方高寒地区的选择与应用 被引量:5

Choice and application of SF_6 breaker switch in north cold climate regions
下载PDF
导出
摘要 SF6高压断路器具有良好的灭弧性能,可提高供电可靠性及减少检修次数,使电气接线形式简单、运行维护方便;但SF6气体遇超低温易液化,严重制约了SF6断路器在北方的正常使用。通过对国产几种典型SF6断路器性能的分析和用户使用情况的调研,证明了在灭弧室内按比例充入SF6混合气体后,可解决SF6气体易液化的问题,确保SF6断路器可在北方寒冷气温下稳定运行。 High voltage SF_6 breaker switch has an excellent arc extinguishing performance, which can promote the reliability of power supply, cut down the times of overhaul, and make the electricity connection type simple and run & maintenance convenience. However, SF_6 gas is apt to liquidize when pumped into extra-low temperature climate, due to which SF_6 breaker switch is restricted badly to use in north areas. Through the performance analysis of several typical kinds of SF_6 breaker switches made by manufactures at home and the survey of customers use circumstance, it is shown that the problems of SF_6 gas liquefaction can be solved when mixed SF_6 gas is put into arcing chamber at appropriate proportion and make SF_6 breaker switch run steady in north cold temperature climate.
出处 《黑龙江电力》 CAS 2004年第6期425-427,共3页 Heilongjiang Electric Power
关键词 SF6断路器 高寒地区 混合气体 稳定运行 SF_6 breaker switch extremely cold areas mixed gas steady operation
  • 相关文献

参考文献5

  • 1[1]张重锁.电力工程电气设备手册[M].北京:中国电力出版社,1998.
  • 2[3]GB 8905-1996,六氟化硫电气设备中气体管理和检测导则[S].
  • 3[4]DI/T595-1996,六氟化硫电气设备气体监督细则[S].
  • 4[5]DI/T405-1996,进口252(245)-550 kV交流高压断路器和隔离开关技术规范[S].
  • 5[6]DI/T615-1997,交流高压断路器参数选用导则[S].

同被引文献54

引证文献5

二级引证文献15