摘要
根据背靠背直流系统的技术特点 ,详细计算了由于触发不平衡和交流系统正序二次谐波在换流变压器中产生的直流偏磁电流。计算结果表明 ,2 2 0kV和 330kV侧每台换流变压器网侧绕组中最大等效直流电流的计算值分别为 5 .2和 3.5A ,符合设计要求。
The DC biasing current has been calculated in detail, which will go through the converter transformer winding in BTB DC system due to unbalance firing and the second harmonic voltage of positive sequence on the AC converter bus. Converted to the winding of transformer the equivalent DC current through each converter transformer is 5.2 A and 3.5 A respectively on 220 kV and 330 kV side, which meets the design specification.
出处
《高电压技术》
EI
CAS
CSCD
北大核心
2004年第11期48-49,共2页
High Voltage Engineering
关键词
换流变压器
直流偏磁电流
converter transformer
DC biasing current