摘要 提出的电流互感器误差低压外推测试法,是将现场电流互感器当作误差相同的电压互感器进行测试,先在200%~1000%额定电压(电流)下测互感器的误差和导纳等参数,再通过在1%~120%额定电压(电流)下测导纳,进而由公式推算出电流互感器的误差。测试结果表明与传统方法相符,故这种新方法的推广、应用将对现场电流互感器的检定产生深远的影响。 It is described in this paper, the error of current transformers could be tested by using deduced method, a current transformer could be tested as a v oltage transformer with the same error. At first, error and admittance could be tested at 200% to 1000% rated voltage(current), then error could be obtained aft er the calculation and the admittance tested at 1% to 120% rated voltage(current ). The generalization and application of this new method would bring a great eff ect to the calibration of locale current transformers.
出处 《电测与仪表》 北大核心 2004年第12期28-30,共3页 Electrical Measurement & Instrumentation
关键词 电流互感器 电压互感器 误差 外推法 current transformer voltage transformer error deduced method