摘要
针对变电所消弧线圈接地系统在正常运行情况下中性点位移电压长时间偏高现象,进行了分析。定量地估算了系统实际不对称电压值,提出通过降低不对称电压U0,增大消弧线圈的脱谐率v和增大电网的阻尼率d等方法可降低消弧线圈接地系统中性点位移电压,从而保证消弧线圈的正常工作。
The abnormal phenomenon of long time higher neutral voltage shift in a substation is analyzed,which is grounded through arc suppression coil. The actual asymmetrical voltage is quantita-tively estimated. Three methods to lower the neutral voltage shift are presented,lowering the asym-metrical voltage U0,increasing resonant deduction rate v and increasing the damping ratio d,which ensure the normal operation of arc suppression coil.
出处
《电力自动化设备》
EI
CSCD
北大核心
2005年第1期93-94,共2页
Electric Power Automation Equipment
关键词
消弧线圈
中性点位移电压
接地系统
arc suppression coil
neutral voltage shift
earthing system