补偿电网阻尼率及脱谐度问题研究 被引量:9

Study on damping rate and out-of-resonance degree of power compensation network
下载PDF
导出
摘要 阻尼率和脱谐度是补偿电网的两个重要参数。针对补偿电网运行中出现的虚幻接地、三相电压不平衡等问题,分别从中性点位移电压、三相电压不平衡度以及残流的有功分量、无功分量等方面,分析了阻尼率和脱谐度对补偿电网运行特性的影响,推导出了阻尼电阻和脱谐度的配置公式,也解决了运行中出现的此类问题。 Damping rate and out-of-resonance degree are two important parameters of power compensation network. To resolve the existing problems on these two parameters, such as virtual earth and three-phase unbalanced voltages, this paper analyses some influence on power compensation network operation characteristics due to the changes of damping rate and out-of-resonance degree in some aspects, like neutral-to-ground voltage, unbalanced degree on the three-phase voltages, and component of residual current. It also gives reasonable formulae for setting damping rate and out-of-resonance degree. The adoption of these research methods also solves actual operation of arc-suppression coils concerned.
出处 《继电器》 CSCD 北大核心 2005年第4期36-39,44,共5页 Relay
关键词 补偿电网 消弧线圈 阻尼率 脱谐度 power compensation network arc-suppression coil damping rate out-of-resonance degree
  • 相关文献

参考文献8

二级参考文献28

  • 1张彪.自动跟踪补偿消弧装置在煤矿高压电网中的应用[J].煤矿机电,1993,14(2):53-55. 被引量:2
  • 2蔡旭,李伟民.自动跟踪电网电容电流动态补偿系统研究[J].电力系统自动化,1995,19(8):57-61. 被引量:47
  • 3蔡旭.偏磁式消弧线圈及其动态控制系统的研究:博士学位论文[M].徐州:中国矿业大学,2000..
  • 4江秀臣,李锋,傅正财,李福寿.调匝式消弧线圈自动调谐装置[J].高压电器,1997,33(1):53-56. 被引量:6
  • 5Owen E L. The historical development of neutral grounding practices. IEEE Industry Applications Magazine, 1997, 3(2) : 10 - 20.
  • 6IEEE Guide for the application of Neutral Grounding in Electrical Utility Systems, Part Ⅳ-Distribution. IEEE Std. C62.92.4-1991, 1992.
  • 7邱关源.电路上册[M].高等教教育出版社,1997
  • 8王锡钒,等.电力工程[M].西安交通大学出版社,2000.
  • 9要万年,等.电力系统谐振接地[M].中国电力出版社,2000.
  • 10电力行业标准.交流电气装置的过电压保护和绝缘配合[S].DL/T620-1997.