摘要
超高压输电线路发生故障时 ,线路上的串补电容及其保护回路都将在故障时产生附加的暂态分量 ,本文分析了串补电容对高频暂态量电流的影响 。
Being fault on the Extra High Voltage (EHV) transmission lines, series capacitor compensation and its protection on the lines can cause additional transient component. This paper analyses the effect of series capacitor compensation on faults current's high frequency transient component, proving that series capacitor compensation does not affect the time of high frequency transient current component transmitting from faults point to protector.
出处
《南京工程学院学报(自然科学版)》
2003年第4期64-67,共4页
Journal of Nanjing Institute of Technology(Natural Science Edition)
基金
江苏省高校自然科学研究项目 ( 0 2KJD470 0 0 6)
南京工程学院科研基金项目 (科 0 4-63 )