一种基于时间域的实用单侧电量故障测距方法 被引量:14

A TIME DOMLAN BASED PRACTICAL FAULT LOCATING ALGORITHM USING ONE TERMINAL VOLTAGE AND CURRENT
下载PDF
导出
摘要 分析了现时广泛应用的基于频域的正弦稳态故障测距方法的不足,指出其对网络运行参数过分依赖,介绍了一种不需知道网络运行参数的时域法,同时,利用频域法的优点对其假设条件进行修正,将时域与频域两种方法的优越性有机地结合起来。该方法最少只需四个采样点就可构造出一个简单的关于故障距离的非线性方程组,易于在微机自动化装置上实现。该方法被成功地应用于一种故障录波分析装置。 This paper analyzes the flaws of locating transmission line fault method using sine stable component in frequence domain , points out its dependance of network operating parametres and introduces a time-domain approch which may not know the network porametres. Meantime ,the hypothesis condition is adjusted by frequence-domain method. Therefor , the advantage of two metheds is combined. The algorithmcan construct a set of simple nolinear equations about fault distance with only four sampling values , whichis easily solved with micro-computer. The approch has been successfully applied in a digital faultrecorder.
机构地区 华中理工大学
出处 《电力系统自动化》 EI CSCD 北大核心 1994年第5期52-57,共6页 Automation of Electric Power Systems
关键词 电量 时域 测距 locating fault stable component network parametres time-domain z transform
  • 相关文献

参考文献3

  • 1杨维娜,苏沛浦,杨奇逊.论用于输电线故障测距的数字滤波器的设计[J]华北电力学院学报,1985(04).
  • 2叶一麟,蔡德礼.系统参数变化对输电线路故障测距精度的影响[J]重庆大学学报(自然科学版),1984(04).
  • 3蔡德礼.高压输电线故障点定位的一种新的计算机方法[J]重庆大学学报(自然科学版),1982(02).