期刊文献+

由冷却塔排放烟气脱硫净烟气对循环冷却水水质的影响及其对策研究 被引量:7

INFLUENCE OF PURIFIED FLUE GAS DISCHAR-GING FROM FGD FACILITY THROUGH COOLING TOWER UPON QUALITY OF CIRCULATORY COOLING WATER AND STUDY ON COUNTER MEASURES THE REOF
下载PDF
导出
摘要 通过冷却塔排放湿法烟气脱硫净烟气,会使一定量的污染物进入循环冷却水系统,导致循环水杂质增加,pH值降低,电导率升高,系统腐蚀速度加快。对此,防治措施为加入合适的化学药品,以及合理选材和控制凝汽器管内流速,加强运行监测。此外,有条件的电厂应定期进行清理,必要时采用技术经济合理的旁流处理形式。 The purified flue gas discharging from flue gas desulfuration (FGD)facility through cooling tower can make a certain pollutants coming into circulatory cooling water system,leading to enhancement of impurities in circulating water,reduction of its pH value,increasement of its electric conductivity,and acceleration of system corrsion speed.The remedial counter measures are as follows:dosing suitable chemical agents;as well as suitably selecting materials and controlling the flow rate in condenser tubes;and strengthening monitor in operation,carrying out periodic cleaning in power plants with conditions exist,and adopting the by-pass flow treatment reasonable in technical and economical aspects if necessary.
出处 《热力发电》 CAS 北大核心 2005年第3期61-64,73,共5页 Thermal Power Generation
关键词 烟塔 净烟气 排放 循环冷却水 水质 flue gas discharging tower purified flue gas discharging circulatory cooling water water quality
  • 相关文献

参考文献6

  • 1GBS0050-95.工业循环冷却水设计规范[S].[S].,..
  • 2GB50046—95.工业建筑防腐蚀设计规范[S].[S].,..
  • 3.中国环境影响评价法与规划、设计、建设项目实施手册(第二卷)[M].中国环境出版社,2002..
  • 4国电热工研究院.利用城市污水作为电厂循环水的补充水的研究报告[R].,1995..
  • 5.火电厂水务管理[M].国家电力公司,1998..
  • 6杨东方.火电厂循环冷却水处理[M].中国电力出版社,2002..