深圳公共场所集中空调通风系统卫生学评价 被引量:9

深圳公共场所集中空调通风系统卫生学评价
下载PDF
导出
摘要 目的:调查评价公共场所集中空调通风系统污染状况,为卫生管理提供依据。方法:随机抽取深圳市各类公共场所2 0个集中空调通风系统,检查各部件清洁度;检测新风量、冷却水中军团菌及空调送风中可吸入颗粒物、细菌总数、真菌总数、溶血性链球菌含量。结果:2 0个空调系统的2 50个部件中,2 4 %有尘粒,5 %有污垢,未发现菌癍;有35 %空调系统新风量未达到卫生标准要求;空调送风中污染物的平均日均值分别为:可吸入颗粒物0 . 1 2mg/m3,细菌总数2 91cfu/m3,总数2 .73cfu/m3,未检出溶血性链球菌;分别有1 0 %、5 %的空调系统送风中可吸入颗粒物、细菌总数超标;采集50份冷却塔水样,未检出军团菌。结论:公共场所集中空调通风系统仍存在卫生问题,应加强卫生管理。 Objective:To investigate the pollution of ventilating system in air condition in public in order to present evidence to hygiene management. Methods:To take out 20 ventilating system in air condition from every kind of public in Shenzhen and check the sweep degree of each part: To exam new breeze,measure the legionella in cooling tower water, PM10,aerobic bacterial count,aerobic molds count and the content of staplococcus hewolyticus in the air. Results:250 parts from 20 air condition system,24% of them had dust?5%had bilge,but no milden; 35%new breeze measure of air Condition system is over the hygiene standard;The total average of the pollution in air condition are:PM10 is 0.12mg/m 3,aerobic bacterial count is 291cfu/m 3,aerobic molds count is 273cfu/m 3and sterptococcus hemolylicus not be checd out ;10%PM10 and 5% aerobic bacterial count is over the standard; legionella not be found in 50 cooting tower water. Conclusion :The results indicate that the problem have even existed in the ventilating system in public. the hygiene management must be go on enhaneing.
出处 《中国公共卫生管理》 2005年第2期164-165,共2页 Chinese Journal of Public Health Management
  • 相关文献

参考文献4

二级参考文献19

  • 1陈悦.军团菌实验室快速诊断技术的建立[J].上海预防医学,1999,11(9):398-400. 被引量:9
  • 2陈悦,沈健民,何智纯,姜华.上海地区军团菌感染和环境污染状况的调查[J].上海预防医学,2000,12(7):305-306. 被引量:46
  • 3American Society of Heating, Refrigerating and Aironditioning Engineels. Inc. 1999, Ventilation for acceptable indoor air quality. ASHRAE 62- 1999.
  • 4Brown K S. Sick Days at Work[ J]. Environmental Health Perspectives, 1996,104:1032- 1035.
  • 5Burge H A K, Kreiss P R. Morey J, et.al. Guidelines for Assessment and Sampling of Saprophytic Bioaerosols in the Indoor Environment[ J ]. Applied Industrial Hygiene, 1987,2(5) :R10- R16.
  • 6Department of Building Services Engineering Hong Kong Polytechnic University 2000, Good practice guide to indoor air quality for hotels in Hong Kong. Hong Kong Polytechnic University Press.
  • 7Fanger P O, Bluyssen P, Clausen G, et al. Air Pollution Sources in Offices and Assembly Halls[J]. Energy Buildings,1988,12:7 - 19.
  • 8Greene R E, Casey J M, Williams P L.A Proactive Approach for Managing Indoor Air Quality[J]. J Enviromnental Health,1997,60(11) : 15 - 21.
  • 9Hodgson M J, Frohlinger J, Karpf M, et al. Symptoms and Microenvironmental Measures in Nonproblem Buildings[ J]. J Occupational Medicine, 1991,33:527 - 533.
  • 10Indoor Air Quality Management Group of the Government of HKSAR. Guidance notes on managing indoor air quality in air-conditioned buildings and public places. Hong Kong,2000.

共引文献118

同被引文献85

引证文献9

二级引证文献27

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部